null

WAGO 787-1002

(No reviews yet) Write a Review
SKU:
787-1002
Condition:
New
  • Wago 787-1002
  • Wago 787-1002
  • Wago 787-1002
$89.93

Description

EPSITRON COMPACT power supply; single-phase; output voltage 24 VDC; 1.3 A
View AllClose

Additional Information

conformity marking:
CE
connection technology:
CAGE CLAMP
connection type 1:
Input/output
control deviation:
¤ 2 %
country of origin sales organisation germany:
CN
current limitation:
1.1 x Io nom (typ.)
default setting:
DC 24 V
depth:
59 mm / 2.323 inch
depth from upper edge of din rail:
55 mm / 2.165 inch
derating:
-3 %/K (> 45 C)
discharge current:
¤ 1 mA
efficiency typ:
0.82
fine stranded conductor:
0.08 2.5 mm / 28 12 AWG
fire load:
0.000 MJ
flammability class per ul94:
V0
height:
89 mm / 3.504 inch
input current ii:
¤ 0.5 A (230 VAC): ¤ 0.7 A (110 VAC)
input voltage derating:
Io ¤ 1 A (< 100 VAC)
input voltage range:
AC 85 264 V: DC 120 373 V
inrush current:
¤ 30 A (NTC)
internal fuse:
T 2 A / 250 VAC
isolation voltage pri sec:
DC 4.242 kV
mains failure hold up time:
80 ms (230 VAC): 10 ms (110 VAC)
mounting type:
DIN-35 rail
mtbf:
> 500,000 h (per IEC 61709)
nominal input voltage ui nom:
1 x AC 100 240 V
nominal mains frequency range:
44 66 Hz: 0 Hz
nominal output current io nom:
1.3 A (24 VDC): 0.9 A (in any mounting position)
nominal output power:
31.2 W
nominal output voltage uo nom:
DC 24 V (SELV)
open circuit proof:
Yes
operation status indicator:
Green LED (Uo)
output voltage range:
DC 22.8 26.4 V (adjustable)
overload behavior:
Constant current
overvoltage category:
II
overvoltage protection secondary:
¤ 40 VDC (in the event of a fault)
packaging type:
Box
parallel operation:
Yes
phases:
1
pollution degree:
2
power factor correction pfc:
Passive
power loss max pl max:
7.3 W (100 VAC / 24 VDC: 1.3 A)
power loss pl:
¤ 2.6 W (230 VAC: No load): ¤ 7 W (230 VAC: Nominal load)
protection class:
II
protection type:
IP20 (per EN 60529)
recommended backup fusing:
Circuit breaker: 6 A (C characteristic), 10 A (B characteristic) or higher
relative humidity:
5 96 % (no condensation permissible)
required backup fusing:
An external DC fuse is required for the DC input voltage.
residual ripple:
¤ 100 mV (Peak-to-peak)
resistance to reverse feed:
¤ DC 30 V
series operation:
Yes
short circuit protected:
Yes
signaling:
1 x Status indication LED (green)
solid conductor:
0.08 2.5 mm / 28 12 AWG
standards specifications:
EN 61010-1 || EN 61010-2-201 || EN 61204-3 || UL 60950-1 || UL 508 || DNV GL
strip length:
6 7 mm / 0.24 0.28 inch
surrounding air operating temperature for ul:
-25 55 C
surrounding air temperature operation:
-25 60 C (Device starts at 40 C (type-tested))
surrounding air temperature storage:
-25 80 C
transient suppression primary:
Varistor
wago connector:
WAGO 740 Series
weight:
180.000 g
width:
54 mm / 2.126 inch
View AllClose