WAGO 787-1002
- SKU:
- 787-1002
- Condition:
- New
Additional Information
conformity marking: |
CE |
connection technology: |
CAGE CLAMP |
connection type 1: |
Input/output |
control deviation: |
¤ 2 % |
country of origin sales organisation germany: |
CN |
current limitation: |
1.1 x Io nom (typ.) |
default setting: |
DC 24 V |
depth: |
59 mm / 2.323 inch |
depth from upper edge of din rail: |
55 mm / 2.165 inch |
discharge current: |
¤ 1 mA |
efficiency typ: |
0.82 |
fine stranded conductor: |
0.08 2.5 mm / 28 12 AWG |
fire load: |
0.000 MJ |
flammability class per ul94: |
V0 |
height: |
89 mm / 3.504 inch |
input current ii: |
¤ 0.5 A (230 VAC): ¤ 0.7 A (110 VAC) |
input voltage range: |
AC 85 264 V: DC 120 373 V |
inrush current: |
¤ 30 A (NTC) |
internal fuse: |
T 2 A / 250 VAC |
isolation voltage pri sec: |
DC 4.242 kV |
mains failure hold up time: |
80 ms (230 VAC): 10 ms (110 VAC) |
mounting type: |
DIN-35 rail |
mtbf: |
> 500,000 h (per IEC 61709) |
nominal input voltage ui nom: |
1 x AC 100 240 V |
nominal mains frequency range: |
44 66 Hz: 0 Hz |
nominal output current io nom: |
1.3 A (24 VDC): 0.9 A (in any mounting position) |
nominal output power: |
31.2 W |
nominal output voltage uo nom: |
DC 24 V (SELV) |
open circuit proof: |
Yes |
operation status indicator: |
Green LED (Uo) |
output voltage range: |
DC 22.8 26.4 V (adjustable) |
overload behavior: |
Constant current |
overvoltage category: |
II |
overvoltage protection secondary: |
¤ 40 VDC (in the event of a fault) |
packaging type: |
Box |
parallel operation: |
Yes |
phases: |
1 |
pollution degree: |
2 |
power factor correction pfc: |
Passive |
power loss max pl max: |
7.3 W (100 VAC / 24 VDC: 1.3 A) |
power loss pl: |
¤ 2.6 W (230 VAC: No load): ¤ 7 W (230 VAC: Nominal load) |
protection class: |
II |
protection type: |
IP20 (per EN 60529) |
recommended backup fusing: |
Circuit breaker: 6 A (C characteristic), 10 A (B characteristic) or higher |
relative humidity: |
5 96 % (no condensation permissible) |
required backup fusing: |
An external DC fuse is required for the DC input voltage. |
residual ripple: |
¤ 100 mV (Peak-to-peak) |
resistance to reverse feed: |
¤ DC 30 V |
series operation: |
Yes |
short circuit protected: |
Yes |
signaling: |
1 x Status indication LED (green) |
solid conductor: |
0.08 2.5 mm / 28 12 AWG |
standards specifications: |
EN 61010-1 || EN 61010-2-201 || EN 61204-3 || UL 60950-1 || UL 508 || DNV GL |
strip length: |
6 7 mm / 0.24 0.28 inch |
surrounding air temperature operation: |
-25 60 C (Device starts at 40 C (type-tested)) |
surrounding air temperature storage: |
-25 80 C |
transient suppression primary: |
Varistor |
wago connector: |
WAGO 740 Series |
weight: |
180.000 g |
width: |
54 mm / 2.126 inch |