Eden DYN Info, Reset and Status

Eden communicates with a dynamic signal generated by the control device, a Vital, a Pluto Safety PLC or a URAX. Up to 30 Eden sensors can be connected in series to Vital 1. Ten Eden sensors can be connected to one Pluto or URAX input, without reducing the achieved performance level. It is also possible to connect safety light beams, Tina adaptor units and E-stops in the same safety circuit. Adam and Eva are acquired separately and it is possible to mix different models of Adam DYN in the same safety circuit.

Eden DYN consists of an Adam DYN and an Eva (general or unique code). Adam DYN uses the ABB Jokab Safety DYNlink signal that allows to connect several safety products in series while maintaining PL e using only one channel. DYNlink signals must be used with Vital safety controller or Pluto safety PLC. Up to 30 Adam DYN can be connected in series to Vital and up to 10 Adam DYN can be connected in series to one input of Pluto. All products using the DYNlink signal can easily be connected in series and mixed in the same loop with a maintained PL e. Tina adapters allow to use other products in a DYNlink loop, and a wide range of connection accessories simplifies the cabling.

Eden DYN Instruction Manual