Description
Technical Data
Construction
Description
SUPERFLEX?? N (C) PVC
Jacket material
Special PVC
Jacket color
grey RAL 7001
Outer ?????
12,4 mm
Outer ?????
0,488 inch
Weight
201 Lbs/Mft
Cu-Index
90 Lbs/Mft
Element 1
Element construction
AWG 16 / 1,5 mm??«
Conductor
CU-wire bare
Conductor category
- Superfinely stranded DIN VDE 0295
- IEC 60228, Class 6
Conductor marking
- black
- with white number print
- green/yellow
Conductor insulation
Special TPE
overall construction
Overall stranding
- conductors twisted without mechanical stress
- layer pitch optimised
Overall wrapping
Fleece taping
Inner jacket
PVC
Overall shield
- Tinned copper wires
- Braid shield
- optical cover approx. 85%
Jacket characteristics
- abrasion resistant
- tough
- tear resistant
- microbe resistant
- hydrolysis-resistant
- rot-resistant
- UV resistant (normal lighting conditions)
- Oil resistant
- Silicone-free
- Flame-retardant
Technical data
Rated voltage UN
600 V UL AWM 105 ???C
Test voltage type
3000V
Temperature range moving
-15 ???C ?? +90 ???C
Temperature range fixed
-40 ???C ?? +105 ???C
Minimum bending radius moving
10?????D
Minimum bending radius fixed
6?????D
Element 1
Element construction
AWG 16 / 1,5 mm??«
Insulation resistance at 20 ???C
100 M??????km
Approvals/Standards
Approvals
- cURus
- AWM I/II A/B 105???C 600V FT1
UL style
AWM 2586
Conformity
- RoHS
- 2015/863/EU
- CE
- REACH
Burning behavior according to
- UL VW1, FT1
- DIN EN 50265-2-1
Oil resistant according to
- UL 4d100C
- UL Oil Res 80 ???C
- DIN EN 60811-2-1
UV-resistant according to
DIN EN ISO 4892-2-A
General
Note
CE These products are in conformity with the EU Low Voltage Directive 2014/35/EU
Machine and device construction, transport and conveyor technology, HVAC technology In dry and damp rooms As a monitoring, measurement and control cable for industrial applications For installation in energy chains with constant linear movement Anywhere where electrical interference fields can influence the signal transmission