Description
Technical Data
Note
Included in the delivery
Plug-in terminal black, RM 5.08, 3-pin, 2.5 mm2
Not included in the delivery
other accessories, see ???accessories???
Communication
Standard
IEEE 802.3, 802.3u, 802.3x
LAN
10 / 100 Base-TX
Cable length (segment)
Max. 100 m
Transfer rate
max. 100 Mbit/s
Connection technology (data)
8 ?? RJ45
Status display communication
Link activity
Safety
Reverse voltage protection
Yes
Isolating voltage Ethernet/supply/FE
1000 V
General
Rated voltage UN
AC/DC 24 V (SELV, PELV)
Rated frequency fN
50/60 Hz with AC supply
External fuse
3 A
Operation voltage range
AC 19.2???28.8 V / DC 18???31.2 V
Connection technology (supply)
3-pin terminal clamp, push-in, RM 5.08 or via LCOS-FT Powerbus
Power consumption
1,6 W
Protection class
IP20
Over voltage category
II
Degree of polution
2
Application height
2000 m
Relative humidity (operation)
5 % - 95 % (non-condensing)
Relative humidity (storage)
0 % - 95 % (non-condensing)
Operation temperature range
-25 ???C ??? +70 ???C
Storage temperature range
-40???C???85???C
Dimensions (w ?? h ?? d)
35??110??102 mm
Housing material
PA 6.6 (UL 94 V-0, NFF I2, F2)
Mounting
can be connected to LCOS function carrier 35 mm (accessories), hat rail mounting EN 60715
Installation position
vertical
Standards
- EN 61131-2:2007
- IEC 61000-6-2:2016
- IEC 61000-6-4:2018
Approvals
- CE
- cULus (E170585)
- DNV GL
PU
1 piece
Accessories
- Function carrier 35 mm, cannot be expanded with modules: Part.-No. 780201.350.1 | LCOS-FT-PE-350-00-00-1 | PU: 1 unit
- Function carrier 35 mm, can be expanded with modules: Part.-No. 780402.350.1 | LCOS-FT-PE-350-0P-02-1 | PU: 1 unit
- Function carrier 70 mm, with power supply DC 24 V, no FBS, plug-and-play: Part.-No. 780700.700.1 | LCOS-FTE-PE-700-NC-00-1 | PU: 1 unit
- Side cover plate for function carrier: Part.-No. 780600.000.4 | LCOS-ZB-AD-00-1 | PU: 100 units
- Power bridge 1-pin insulated: Part.-No. 780961.001.2 | LCOS-ZB-PB-01-00 | PU: 10 units
Note
For AC supply, there must be external over-voltage protection that limits the voltage between the supply and the FE to below 1000 V.