Description
Technical Data
Input
Input variable
Analogue signals
Measurement input
- +30/-30 V, +50/-50 mA, DC +5 A/-5 A
- adjustable via software FDT/DTM, connection via micro USB
Galvanic isolation I/O
2-way isolation
Step response (10???90%)
4 ms ??? 750 ms (adjustable by means of filter stage 1???5, default: filter stage 4 = 200 ms)
Parameterisation
- Software FDT/DTM
- DIP switch
Zero /Span
freely adjustable
Input resistance
>800 k? @ +30/-30 V, 30 ? @ +50/-50 mA, 10 m? @ DC +5 A/-5 A
Output
Output signal
+30/-30 V, +50/-50 mA, DC +5 A/-5 A, adjustable via software FDT / DTM, connection via USB service cable
Contact type
K1,K2: Semi-conductor, N/O contact
Max. switching voltage
DC 30 V
Max. switching current
DC 100 mA
Status display output
LED yellow K1 and LED yellow K2, not short circuit protected
Operating mode
Limit value, window, alarm output / additionally adjustable: Hysteresis, input / output delay
Parameterisation
- Software FDT/DTM
- DIP switch
Operating data
Accuracy
- 0.1 % FSR @ +30/-30 V, +50/-50 V
- 0.5 % FSR @ +5 A/-5 A
Linearity error
??ñ0.05 % FSR @ +30/-30 V, +50/-50 V
??ñ0,1 % FSR @ +5 A/-5 A
??ñ0,1 % FSR @ +5 A/-5 A
General
Rated voltage UN
DC 24 V
Operation voltage range
16.8???30 V
Rated current
approx. 12 mA
Status indication
LED green, yellow (K1, K2), red (error)
Input/output protection
Overvoltage DC 30 V
Temperature error
<100 ppm FSR
Data storage
Flash
Insulation voltage input / output
2.5 kVeff
Resolution
16-bit
Configuration
Software: FDT / DTM
Housing material
PA 6.6 (UL 94 V-0)
Color of the housing
light grey
Mounting
- DIN rail mountable TS35
- (EN 60715)
Protection class
IP20
Installation position
any
Connection type
- Screw terminal
- 0.14 mm2 ??? 1.5 mm2
Operation temperature range
-40 ???C ??? +70 ???C
Storage temperature range
-40???C???85???C
Dimensions (w ?? h ?? d)
6,2??90??115,5 mm
Weight
0,05 kg/piece
PU
1 piece
Approvals
- cULus (E135145)
- Cl.1 Div2, Gr. A, B, C, D, T4A
- GL
Standards
EN 60947-5-1