24 Vdc nominal output adjustable from 24–28 Vdc, providing 5 A at 24 V and 4.3 A at 28 V for flexible load matching.
120 W continuous output power with 20% Power Boost for starting higher inrush loads and providing short‑term extra capacity.
Low ripple and noise (max. 50 mVpp) to protect sensitive PLCs, analog I/O, sensors, and communication equipment.
Wide AC input range of 100–240 Vac (‑15% / +10%) and DC input range of 110–150 Vdc (±20%), supporting global mains and DC bus applications.
Active power factor correction with power factor around 0.91 and active inrush current limitation (4 A / 4 A) to minimize input surges and upstream stress.
Recommended external input fuse B‑6 A or C‑6 A simplifies selection of upstream protection devices.
Slim 32 x 124 x 102 mm housing to maximize DIN rail density in compact control cabinets.
DIN rail mounting with screw terminal connections for secure, proven wiring in industrial environments.
Operating temperature range from ‑25 °C to +70 °C with derating of 3 W/°C above 60 °C; full rated power available up to 60 °C.
Typical efficiency of 94.3% reduces heat generation to about 7.3 W at full load, easing cabinet cooling and improving reliability.
High MTBF of about 867,000 h at 40 °C (SN 29500) supports long‑term 24/7 operation in industrial environments.
Integrated DC‑OK relay contact enables remote monitoring of output status by PLCs or supervisory systems.