Schneider Electric ATV630D90Y6 Atv630Ip00 90Kw 500V-690V Variable Spee
Schneider Electric
$16,746.84
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. This variable speed drive features an integrated EMC filter with 25m cable conforming to category C3. It works at a rated supply voltage from 500V to 690VAC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 90kW/125HP (500V supply voltage) for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 75kW/100HP (500V supply voltage) for applications requiring significant overload (up to 150%). Its dimensions are 331mm (width) x 297mm (depth) x 630mm (height). It weighs 53kg. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. This product is certified by CE, CSA and TUV. It meets UL 508C, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508 and IEC 13849-1 standards. Accessories (fan kit, graphic display terminal) and options (line chokes, dv/dt filter, sinus filter, EMC filter) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
- Line Current:
- 108.3 A 500 V normal duty) || 99.4 A 690 V normal duty) || 82.7 A 500 V heavy duty) || 87.7 A 690 V heavy duty)
- Motor Power Kw:
- 75 kW 500 V normal duty) || 55 kW 500 V heavy duty) || 90 kW 690 V normal duty) || 75 kW 690 V heavy duty)
- Braking To Standstill:
- by DC injection
- Frequency Resolution:
- display unit 0.1 Hz || analog input 0.012/50 Hz
- Local Signalling:
- for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
- Maximum Transient Current:
- 124.5 A 60 s heavy duty) || 118.8 A 60 s normal duty)
- Net Weight:
- 53 kg
- Type Of Polarization:
- no impedance
- Minimum Switching Current:
- relay output R1, R2, R3 5 mA 24 V DC
- Mounting Mode:
- wall mount
- Relay Output Type:
- configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
- Electrical Connection:
- control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 50 mm² AWG 1 || line side screw terminal 50 mm² AWG 1
- Method Of Access:
- slave Modbus TCP
- Linearity Error:
- AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
- Switching Frequency:
- 1...4.9 kHz adjustable || 2.5...4.9 kHz with derating factor
- Vibration Resistance:
- 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
- Power Dissipation In W:
- natural convection 320 W 500 V 2.5 kHz || forced convection 1433 W 500 V 2.5 kHz
- Number Of Addresses:
- 1-247 Modbus serial
- Permissible Temporary Current Boost:
- 1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
- Pollution Degree:
- 2
- Maximum Switching Current:
- relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2
- Transmission Rate:
- 10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
- Sustainable Offer Status:
- Green Premium product
- Ambient Air Temperature For Storage:
- -40-70 °C
- [Us] Rated Supply Voltage:
- 500...690 V
- Analogue Input Type:
- AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
- Pollution Degree:
- 2 IEC 61800-5-1
- Exchange Mode:
- half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
- Analogue Input Number:
- 3
- Type Of Cooling:
- forced convection
- Product Destination:
- asynchronous motors || synchronous motors
- Depth:
- 297 mm
- Sampling Duration:
- 2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
- Accuracy:
- +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
- China Rohs Regulation:
- X
- Connector Type:
- RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
- Acceleration And Deceleration Ramps:
- linear adjustable separately from 0.01...9999 s || S, U or customized
- Height:
- 630 mm
- Product Or Component Type:
- variable speed drive
- Transmission Frame:
- RTU
- Maximum Horse Power Rating:
- 100 hp 500 V normal duty || 75 hp 500 V heavy duty || 125 hp 690 V normal duty || 100 hp 690 V heavy duty
- Communication Port Protocol:
- Modbus TCP || Modbus serial || Ethernet
- Discrete Input Logic:
- positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
- Ip Degree Of Protection:
- IP00IEC 61800-5-1 || IP00IEC 60529 || IP20 with kit VW3A9706)IEC 61800-5-1 || IP20 with kit VW3A9706)IEC 60529
- Regulation Loop:
- adjustable PID regulator
- Apparent Power:
- 118.8 kVA 690 V normal duty) || 104.8 kVA 690 V heavy duty)
- Prospective Line Isc:
- 70 kA
- [Us] Rated Supply Voltage:
- 500...690 V - 15...10 %
- Noise Level:
- 52 dB 86/188/EEC
- Enclosure Mounting:
- wall mounted
- Device Short Name:
- ATV630
- Operating Altitude:
- <= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Shock Resistance:
- 15 gn 11 ms IEC 60068-2-27
- Overvoltage Category:
- III
- Upgradeability:
- Upgraded components available
- Discrete Input Type:
- DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
- Speed Drive Output Frequency:
- 0.1-500 Hz
- Output Voltage:
- <= power supply voltage
- Marking:
- CE
- Environmental Disclosure:
- ENVPEP1706016EN
- Product Specific Application:
- process and utilities
- Width:
- 331 mm
- Relay Output Number:
- 3
- Emc Filter:
- integrated 25 m IEC 61800-3 category C3
- Supply Frequency:
- 50...60 Hz - 5...5 %
- Option Card:
- slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A c
- Range Of Product:
- Altivar Process ATV600
- Asynchronous Motor Control Profile:
- variable torque standard || optimized torque mode || constant torque standard
- Volume Of Cooling Air:
- 406 m3/h
- Ambient Air Temperature For Operation:
- -15-50 °C without derating) || 50-60 °C with derating factor)
- Quantity Per Set:
- 1
- Data Format:
- 8 bits, configurable odd, even or no parity
- Safety Function:
- STO (safe torque off) SIL 3
- Input Compatibility:
- DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
- Discrete Output Type:
- relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
- Discrete Output Number:
- 0
- Noise Level:
- 56 dB
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Phase:
- 3 phase
- Protection Type:
- thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
- Supply:
- external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
- Circularity Profile:
- ENVEOLI1706016EN
- Continuous Output Current:
- 83 A 2.5 kHz heavy duty || 108 A 2.5 kHz normal duty
- Operating Position:
- vertical +/- 10 degree
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Synchronous Motor Control Profile:
- permanent magnet motor || synchronous reluctance motor
- Insulation Resistance:
- > 1 MOhm 500 V DC for 1 minute to earth
- Maximum Output Frequency:
- 500 kHz
- Discrete Input Number:
- 8
- Analogue Output Type:
- software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
- Standards:
- UL 508C || IEC 61800-3 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
- Isolation:
- between power and control terminals
- Discrete Input Logic:
- 16 preset speeds
- Motor Slip Compensation:
- automatic whatever the load || can be suppressed || not available in permanent magnet motor law || adjustable
- Electromagnetic Compatibility:
- electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
- Nominal Switching Frequency:
- 2.5 kHz
- Refresh Time:
- relay output R1, R2, R3)5 ms +/- 0.5 ms)
- Maximum Thdi:
- <48 % with external line choke IEC 61000-3-12
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Physical Interface:
- Ethernet || 2-wire RS 485
- Analogue Output Number:
- 2
- Relative Humidity:
- 5-95 % without condensation IEC 60068-2-3
- Product Certifications:
- CSA || TÃV || UL
- Variant:
- standard version
- Brochure:
- View
- Catalog:
- View
- Datasheet: