Schneider Electric ATV630U55Y6 Atv630Ip00 5,5Kw 500V-690V Variable Spe
Schneider Electric
$2,873.68
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. This variable speed drive features an integrated EMC filter with 25m cable conforming to category C3. It works at a rated supply voltage from 500V to 690VAC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 5.5kW/7.5HP (500V supply voltage) for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 4kW/5HP (500V supply voltage) for applications requiring significant overload (up to 150%). Its dimensions are 246mm (width) x 242mm (depth) x 420mm (height). It weighs 22kg. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. This product is certified by CE, CSA and TUV. It meets UL 508C, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508 and IEC 13849-1 standards. Accessories (fan kit, graphic display terminal) and options (line chokes, dv/dt filter, sinus filter, EMC filter) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
- Mounting Mode:
- wall mount
- Net Weight:
- 22 kg
- Environmental Disclosure:
- ENVPEP1704001EN
- Overvoltage Category:
- III
- Maximum Transient Current:
- 7.9 A 60 s normal duty) || 8.1 A 60 s heavy duty)
- Range Of Product:
- Altivar Process ATV600
- Analogue Input Number:
- 3
- Analogue Output Type:
- software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
- Operating Altitude:
- <= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
- Product Destination:
- asynchronous motors || synchronous motors
- Output Voltage:
- <= power supply voltage
- Acceleration And Deceleration Ramps:
- linear adjustable separately from 0.01...9999 s || S, U or customized
- Sampling Duration:
- 2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
- Motor Slip Compensation:
- adjustable || can be suppressed || automatic whatever the load || not available in permanent magnet motor law
- Height:
- 420 mm
- Number Of Addresses:
- 1-247 Modbus serial
- Speed Drive Output Frequency:
- 0.1-500 Hz
- Accuracy:
- +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
- Sustainable Offer Status:
- Green Premium product
- Asynchronous Motor Control Profile:
- constant torque standard || optimized torque mode || variable torque standard
- Analogue Input Type:
- AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
- Linearity Error:
- AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
- Protection Type:
- thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
- Local Signalling:
- for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
- Upgradeability:
- Upgraded components available
- Apparent Power:
- 9.6 kVA 690 V normal duty) || 7.3 kVA 690 V heavy duty)
- Connector Type:
- RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
- Discrete Output Number:
- 0
- Continuous Output Current:
- 7.2 A 4 kHz normal duty || 5.4 A 4 kHz heavy duty
- Isolation:
- between power and control terminals
- Maximum Horse Power Rating:
- 5 hp 500 V normal duty || 7.5 hp 690 V normal duty || 5 hp 690 V heavy duty
- [Us] Rated Supply Voltage:
- 500...690 V
- Power Dissipation In W:
- natural convection 82 W 500 V 4 kHz || forced convection 101 W 500 V 4 kHz
- Regulation Loop:
- adjustable PID regulator
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Braking To Standstill:
- by DC injection
- Input Compatibility:
- DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
- Maximum Output Frequency:
- 500 kHz
- Type Of Polarization:
- no impedance
- Discrete Input Logic:
- positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
- Relative Humidity:
- 5-95 % without condensation IEC 60068-2-3
- [Us] Rated Supply Voltage:
- 500...690 V - 15...10 %
- Marking:
- CE
- Vibration Resistance:
- 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
- Product Specific Application:
- process and utilities
- Maximum Thdi:
- <48 % with external line choke IEC 61000-3-12
- Shock Resistance:
- 15 gn 11 ms IEC 60068-2-27
- Volume Of Cooling Air:
- 330 m3/h
- Method Of Access:
- slave Modbus TCP
- Device Short Name:
- ATV630
- Type Of Cooling:
- forced convection
- Ip Degree Of Protection:
- IP00IEC 61800-5-1 || IP00IEC 60529 || IP20 with kit VW3A9705)IEC 61800-5-1 || IP20 with kit VW3A9705)IEC 60529
- Ambient Air Temperature For Storage:
- -40-70 °C
- Transmission Frame:
- RTU
- Discrete Input Type:
- DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
- Communication Port Protocol:
- Modbus serial || Modbus TCP || Ethernet
- Supply:
- external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
- Product Or Component Type:
- variable speed drive
- Discrete Input Logic:
- 16 preset speeds
- Emc Filter:
- integrated 25 m IEC 61800-3 category C3
- Prospective Line Isc:
- 70 kA
- Safety Function:
- STO (safe torque off) SIL 3
- Discrete Input Number:
- 8
- Synchronous Motor Control Profile:
- permanent magnet motor || synchronous reluctance motor
- Variant:
- standard version
- Line Current:
- 7.9 A 500 V normal duty) || 8 A 690 V normal duty) || 6.2 A 500 V heavy duty) || 6.1 A 690 V heavy duty)
- China Rohs Regulation:
- X
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Ambient Air Temperature For Operation:
- -15-50 °C without derating) || 50-60 °C with derating factor)
- Quantity Per Set:
- 1
- Mercury Free:
- Yes
- Exchange Mode:
- half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
- Motor Power Kw:
- 4 kW 500 V normal duty) || 3 kW 500 V heavy duty) || 5.5 kW 690 V normal duty) || 4 kW 690 V heavy duty)
- Enclosure Mounting:
- wall mounted
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Transmission Rate:
- 10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
- Insulation Resistance:
- > 1 MOhm 500 V DC for 1 minute to earth
- Data Format:
- 8 bits, configurable odd, even or no parity
- Permissible Temporary Current Boost:
- 1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
- Physical Interface:
- Ethernet || 2-wire RS 485
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Frequency Resolution:
- display unit 0.1 Hz || analog input 0.012/50 Hz
- Electromagnetic Compatibility:
- electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
- Maximum Switching Current:
- relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2
- Operating Position:
- vertical +/- 10 degree
- Option Card:
- slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A c
- Pollution Degree:
- 2
- Depth:
- 242 mm
- Width:
- 246 mm
- Noise Level:
- 58 dB
- Electrical Connection:
- control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 4...10 mm² AWG 12...AWG 8 || line side screw terminal 4...10 mm² AWG 12...AWG 8
- Minimum Switching Current:
- relay output R1, R2, R3 5 mA 24 V DC
- Noise Level:
- 52 dB 86/188/EEC
- Rohs Exemption Information:
- Yes
- Pollution Degree:
- 2 IEC 61800-5-1
- Relay Output Type:
- configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
- Phase:
- 3 phase
- Relay Output Number:
- 3
- Circularity Profile:
- ENVEOLI1704001EN
- Product Certifications:
- TÃV || UL || CSA
- Switching Frequency:
- 2...8 kHz adjustable || 4...8 kHz with derating factor
- Analogue Output Number:
- 2
- Refresh Time:
- relay output R1, R2, R3)5 ms +/- 0.5 ms)
- Standards:
- UL 508C || IEC 61800-3 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
- Discrete Output Type:
- relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
- Nominal Switching Frequency:
- 4 kHz
- Supply Frequency:
- 50...60 Hz - 5...5 %
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View