Schneider Electric ATV930D45N4ZU Atv930 T12 Rdy Ip00 60Hp 400V Wo Keypad

(No reviews yet) Write a Review
SKU:
ATV930D45N4ZU
UPC:
3606489740313
Condition:
New
Type Of Polarization:
no impedance Modbus serial
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immu
Product Certifications:
CSA || UL || TÜV
Maximum Deflection Under Vibratory Load (During Operation):
1.5 mm at 2...13 Hz
Relative Symmetric Network Frequency Tolerance:
0.05
Assembly Style:
with heat sink
Brake Chopper Integrated:
TRUE
Marking:
CE
With Safety Function Safe Position (Sp):
FALSE
Discrete Input Logic:
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V || positive logic (source) DI7, DI8), < 0.6 V, > 2.5 V || positive logic (source) STOA, STOB), < 5 V, > 11 V
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
With Safety Function Safely Limited Speed (Sls):
TRUE
Degree Of Protection:
UL type 12
Method Of Access:
slave Modbus TCP
China Rohs Regulation:
X
Upgradeability:
Upgraded components available
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
Regulation Loop:
adjustable PID regulator
Asynchronous Motor Control Profile:
constant torque standard || optimized torque mode || variable torque standard
Transmission Rate:
10/100 Mbit/s Ethernet IP/Modbus TCP || 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
Maximum Thdi:
<48 % from 80...100 % of load IEC 61000-3-12
Standards:
UL 508C || IEC 61800-3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Phase:
3 phase
Line Current:
79.8 A 380 V normal duty) || 67.1 A 380 V heavy duty) || 69.1 A 480 V normal duty) || 59.0 A 480 V heavy duty)
Discrete Output Number:
2
Base Load Current At High Overload:
74.5 A
With Safety Function Safe Direction (Sdi):
FALSE
Base Load Current At Low Overload:
88.0 A
Synchronous Motor Control Profile:
permanent magnet motor || synchronous reluctance motor
Emc Filter:
integrated || with EMC plate option
Motor Slip Compensation:
automatic whatever the load || adjustable || not available in permanent magnet motor law || can be suppressed
Data Format:
8 bits, configurable odd, even or no parity Modbus serial
Pollution Degree:
2
Relay Output Type:
configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 1000000 cycles || configurable relay logic R3 sequence relay NO 1000000 cycles
Ambient Air Temperature For Storage:
-40-70 °C
Maximum Switching Current:
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Depth:
262 mm
Nominal Switching Frequency:
4 kHz
Maximum Acceleration Under Shock Impact (During Operation):
150 m/s² at 11 ms
Maximum Acceleration Under Vibrational Stress (During Operation):
10 m/s² at 13...200 Hz
Connector Type:
2 RJ45 || 1 RJ45
With Safety Function Safe Brake Management (Sbc/Sbt):
TRUE
Number Of Addresses:
1-247
Environmental Class (During Operation):
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
Option Card:
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module
Motor Power Kw:
45.0 kW normal duty || 37.0 kW heavy duty
Data Format:
8 bits, configurable odd, even or no parity
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Ambient Air Temperature For Operation:
-15-50 °C without derating) || 50-60 °C with derating factor)
Communication Port Protocol:
EtherNet/IP || Modbus serial || Modbus TCP
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Braking To Standstill:
by DC injection
Permitted Relative Humidity (During Operation):
class 3K5 according to EN 60721-3
Discrete Input Type:
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
Environmental Disclosure:
ENVPEP2007012EN
Network Frequency:
50-60 Hz
Local Signalling:
local diagnostic 3 LED mono/dual colour) || embedded communication status 5 LED dual colour) || communication module status 2 LED dual colour) || presence of voltage 1 LED red)
Power Dissipation In W:
natural convection 121 W 380 V 4 kHz || forced convection 943 W 380 V 4 kHz
With Safety Function Safe Operating Stop (Sos):
FALSE
Net Weight:
26.5 kg
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
With Safety Function Safe Programmable Logic:
FALSE
Discrete Output Type:
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
Number Of Addresses:
1-247 Modbus serial
Width:
210 mm
Product Specific Application:
process for industrial
Volume Of Cooling Air:
240 m3/h
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
Maximum Output Frequency:
599 Hz
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Electrical Connection:
control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 || line side screw terminal 35...50 mm² AWG 2...AWG 1 || motor screw terminal 50 mm² AWG 1 || DC bus screw terminal 35...50 mm² AWG 3...AWG 1
Maximum Transient Current:
105.6 A 60 s normal duty) || 111.8 A 60 s heavy duty)
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Quantity Per Set:
1
Noise Level:
71.5 dB
With Safety Function Safely Limited Position (Slp):
FALSE
Transmission Rate:
10, 100 Mbits || 4.8 kbps || 9600 bit/s || 19200 bit/s
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
With Safety Function Safe Torque Off (Sto):
TRUE
Range Of Product:
Altivar Process ATV900
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
With Safety Function Safe Speed Monitor (Ssm):
FALSE
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Ip Degree Of Protection:
IP21
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Operating Position:
vertical +/- 10 degree
Vibration Resistance:
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Physical Interface:
Ethernet || 2-wire RS 485
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Maximum Output Voltage:
480.0 V
Rohs Exemption Information:
Yes
Input Compatibility:
DI1...DI8 discrete input level 1 PLC IEC 61131-2 || DI7, DI8 pulse input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
Relay Output Number:
3
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Destination:
synchronous motors || asynchronous motors
Switching Frequency:
2...16 kHz adjustable || 4...16 kHz with derating factor
Discrete Input Number:
10
Type Of Polarization:
no impedance
Ambient Air Transport Temperature:
-40-70 °C
Environmental Characteristic:
chemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
Apparent Power:
57.4 kVA 480 V normal duty) || 49.1 kVA 480 V heavy duty)
Overvoltage Category:
III
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
4 Quadrant Operation Possible:
TRUE
With Safety Function Safe Stop 1 (Ss1):
TRUE
Isolation:
between power and control terminals
With Sft Fct Safe Stop 2 (Ss2):
FALSE
Product Or Component Type:
variable speed drive
Height:
597 mm
Continuous Output Current:
88 A 4 kHz normal duty || 74.5 A 4 kHz heavy duty
Discrete Input Logic:
16 preset speeds
Analogue Output Number:
2
Noise Level:
71.5 dB 86/188/EEC
Circularity Profile:
ENVEOLI2007012EN
Device Application:
Industrial Application
Transmission Frame:
RTU
Prospective Line Isc:
50 kA
Sustainable Offer Status:
Green Premium product
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Mercury Free:
Yes
Mounting Mode:
cabinet mount
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
Variant:
standard version || with braking chopper
Analogue Input Number:
3
$8,112.13

Description

variable speed drive, Altivar Process ATV900, ATV930, 60hp, 380 to 480V, cabinet Integration, IP20, for US
View AllClose