Schneider Electric BDA140805 Molded Case Circuit Breaker 277V 80A

(No reviews yet) Write a Review
SKU:
BDA140805
UPC:
3606481151698
Condition:
New
Connection Pitch:
27 mm
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Range:
PowerPact
[Ics] Rated Service Breaking Capacity:
25 kA 220...240 V AC 50/60 Hz IEC 60947-2
Pollution Degree:
3 IEC 60947-1
Rohs Exemption Information:
Yes
Device Short Name:
BD 080
9 Mm Pitches:
3
Mounting Mode:
I-Line
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Device Application:
distribution
Circuit Breaker Application:
HACR rated
Depth:
89 mm
Breaking Capacity:
25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480Y/277 V AC 50/60 Hz UL 489 || 10 kA 125 V DC 50/60 Hz UL 489 || 14 kA 600/347 V AC 50/60 Hz UL 489
Utilisation Category:
category A
Breaking Capacity Code:
D
[Ue] Rated Operational Voltage:
240 V AC 50/60 Hz UL 489
Awg Gauge:
AWG 14...AWG 2/0 aluminium/copper
Continuous Current Rating:
0.8
Line Rated Current:
80-80 A
Ik Degree Of Protection:
IK07 IEC 62262
Ambient Air Temperature For Operation:
-25-70 °C
Mechanical Durability:
20000 cycles IEC 947-1 Annex K ed 5.2
Mercury Free:
Yes
Circularity Profile:
N/A
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Height:
137 mm
Quantity Per Set:
set of 1
Poles Description:
1P
Control Type:
toggle
Net Weight:
0.6375 kg
Electrical Connection:
I-Line connection, line || lugs, load
Halogen Content Performance:
Halogen free product
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Standards:
NMX J-266 || EN/IEC 60947-5-1 || UL 489 || GB 14048.2 || CSA C22.2 No 5 || EN/IEC 60947-2 || NEMA AB1
Ambient Air Temperature For Storage:
-50-85 °C
Tightening Torque:
3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
Local Signalling:
presence of auxiliary contacts flag green)
Eu Rohs Directive:
Compliant with Exemptions
Mounting Height:
38.1 mm
Width:
27 mm
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Product Or Component Type:
circuit breaker
Network Frequency:
50/60 Hz
Suitability For Isolation:
yes IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Sustainable Offer Status:
Green Premium product
Trip Unit Technology:
thermal-magnetic
Quality Labels:
CE
Environmental Disclosure:
ENVPEP1610005EN
Pvc Free:
Yes
Product Name:
PowerPact B
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Phase Connection:
C
Color:
Gray RAL 7016)
Wire Stripping Length:
20 mm
Ip Degree Of Protection:
front cover IP40 IEC 60529
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
  • Schneider Electric BDA140805 Molded Case Circuit Breaker 277V 80A
  • Schneider Electric BDA140805 Molded Case Circuit Breaker 277V 80A
  • Schneider Electric BDA140805 Molded Case Circuit Breaker 277V 80A
$362.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 80A, 1 pole, circuit breaker has a breaking capacity of 18kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with a C phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose