Schneider Electric BDA24040Y1 Molded Case Circuit Brkr 480Y/277V 40A

(No reviews yet) Write a Review
SKU:
BDA24040Y1
UPC:
3606481151827
Condition:
New
Suitability For Isolation:
yes IEC 60947-2
Device Short Name:
BD 040
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Depth:
89 mm
Quantity Per Set:
set of 1
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
9 Mm Pitches:
6
Environmental Disclosure:
ENVPEP1610005EN
Quality Labels:
CE
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Halogen Content Performance:
Halogen free product
Continuous Current Rating:
0.8
Mounting Height:
76.2 mm
Eu Rohs Directive:
Compliant with Exemptions
Mounting Mode:
I-Line
Control Type:
toggle
Product Or Component Type:
circuit breaker
Net Weight:
0.952 kg
Electrical Connection:
I-Line connection, line || lugs, load
Utilisation Category:
category A
Ip Degree Of Protection:
front cover IP40 IEC 60529
Pvc Free:
Yes
Network Frequency:
50/60 Hz
Width:
54 mm
Circularity Profile:
N/A
Height:
137 mm
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Ambient Air Temperature For Storage:
-50-85 °C
Tightening Torque:
3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
Wire Stripping Length:
20 mm
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mercury Free:
Yes
Line Rated Current:
40-40 A
Local Signalling:
presence of auxiliary contacts flag green)
Standards:
NMX J-266 || GB 14048.2 || UL 489 || CSA C22.2 No 5 || EN/IEC 60947-2 || EN/IEC 60947-5-1 || NEMA AB1
Rohs Exemption Information:
Yes
[Ics] Rated Service Breaking Capacity:
25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
Awg Gauge:
AWG 14...AWG 2/0 aluminium/copper
Connection Pitch:
27 mm
Mechanical Durability:
20000 cycles IEC 947-1 Annex K ed 5.2
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Sustainable Offer Status:
Green Premium product
Breaking Capacity Code:
D
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Number Of Slots:
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
Circuit Breaker Application:
HACR rated
Ambient Air Temperature For Operation:
-25-70 °C
Pollution Degree:
3 IEC 60947-1
Device Application:
distribution
Range:
PowerPact
Poles Description:
2P
[Ue] Rated Operational Voltage:
525 V AC 50/60 Hz UL 489
Phase Connection:
AB
Trip Unit Technology:
thermal-magnetic
Ik Degree Of Protection:
IK07 IEC 62262
Product Name:
PowerPact B
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Color:
Gray RAL 7016)
Breaking Capacity:
25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 10 kA 600Y/347 V AC 50/60 Hz UL 489
  • Schneider Electric BDA24040Y1 Molded Case Circuit Brkr 480Y/277V 40A
  • Schneider Electric BDA24040Y1 Molded Case Circuit Brkr 480Y/277V 40A
  • Schneider Electric BDA24040Y1 Molded Case Circuit Brkr 480Y/277V 40A
$714.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 40A, 2 pole, circuit breaker has a breaking capacity of 18kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose