Device Application:
distribution
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Circuit Breaker Application:
HACR rated
Product Name:
PowerPact B
Number Of Slots:
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
Trip Unit Technology:
thermal-magnetic
Mounting Height:
76.2 mm
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Tightening Torque:
3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
Circularity Profile:
N/A
Environmental Disclosure:
ENVPEP1610005EN
Device Short Name:
BD 040
Color:
Gray RAL 7016)
Wire Stripping Length:
20 mm
Mounting Mode:
I-Line
Mercury Free:
Yes
Ik Degree Of Protection:
IK07 IEC 62262
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Ambient Air Temperature For Storage:
-50-85 °C
Poles Description:
2P
Standards:
UL 489 || EN/IEC 60947-2 || GB 14048.2 || NMX J-266 || EN/IEC 60947-5-1 || CSA C22.2 No 5 || NEMA AB1
Awg Gauge:
AWG 14...AWG 2/0 aluminium/copper
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
9 Mm Pitches:
6
[Ue] Rated Operational Voltage:
525 V AC 50/60 Hz UL 489
Breaking Capacity:
25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600Y/347 V AC 50/60 Hz UL 489 || 10 kA 250 V DC UL 489
Line Rated Current:
40-40 A
Suitability For Isolation:
yes IEC 60947-2
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Halogen Content Performance:
Halogen free product
Ambient Air Temperature For Operation:
-25-70 °C
Breaking Capacity Code:
D
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Or Component Type:
circuit breaker
Width:
54 mm
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Pollution Degree:
3 IEC 60947-1
Phase Connection:
AC
Mechanical Durability:
20000 cycles IEC 947-1 Annex K ed 5.2
Utilisation Category:
category A
Net Weight:
0.952 kg
Connection Pitch:
27 mm
Pvc Free:
Yes
Electrical Connection:
I-Line connection, line || lugs, load
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Range:
PowerPact
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Depth:
89 mm
Local Signalling:
presence of auxiliary contacts flag green)
Ip Degree Of Protection:
front cover IP40 IEC 60529
Height:
137 mm
[Ics] Rated Service Breaking Capacity:
25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
Network Frequency:
50/60 Hz
Quality Labels:
CE
Eu Rohs Directive:
Compliant with Exemptions
Quantity Per Set:
set of 1
Continuous Current Rating:
0.8
Rohs Exemption Information:
Yes
Control Type:
toggle
Sustainable Offer Status:
Green Premium product
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric BDA260402 Molded Case Circuit Breaker 600Y/347V 40
  • Schneider Electric BDA260402 Molded Case Circuit Breaker 600Y/347V 40
  • Schneider Electric BDA260402 Molded Case Circuit Breaker 600Y/347V 40
$810.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600Y/347VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 40A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600Y/347VAC. This circuit breaker has a continuous current rating of 80% with an AC phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose