Schneider Electric BDL46030 Molded Case Circuit Brkr 600Y/347V 30A

(No reviews yet) Write a Review
SKU:
BDL46030
UPC:
3606489863739
Condition:
New
Pollution Degree:
3 IEC 60947-1
Product Or Component Type:
circuit breaker
Continuous Current Rating:
0.8
Ambient Air Temperature For Operation:
-25-70 °C
[Ics] Rated Service Breaking Capacity:
25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
Trip Unit Technology:
thermal-magnetic
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Ip Degree Of Protection:
front cover IP40 IEC 60529
Color:
Gray RAL 7016)
Network Frequency:
50/60 Hz
Circularity Profile:
N/A
Eu Rohs Directive:
Compliant with Exemptions
Depth:
80 mm
Sustainable Offer Status:
Green Premium product
Control Type:
toggle
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Halogen Content Performance:
Halogen free product
Quality Labels:
CE
Utilisation Category:
category A
Wire Stripping Length:
20 mm
Product Name:
PowerPact B
Mechanical Durability:
20000 cycles IEC 947-1 Annex K ed 5.2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Device Short Name:
BD 030
Rohs Exemption Information:
Yes
Mercury Free:
Yes
Suitability For Isolation:
yes IEC 60947-2
Electrical Connection:
Everlink lug, line || Everlink lug, load
Quantity Per Set:
set of 1
[Ue] Rated Operational Voltage:
525 V AC 50/60 Hz UL 489
Device Application:
distribution
Breaking Capacity:
25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600Y/347 V AC 50/60 Hz UL 489 || 10 kA 250 V DC UL 489
Height:
137 mm
Number Of Slots:
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
Ambient Air Temperature For Storage:
-50-85 °C
Circuit Breaker Application:
HACR rated
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Breaking Capacity Code:
D
Range:
PowerPact
Net Weight:
1.441 kg
Line Rated Current:
30-30 A
Width:
108 mm
Connection Pitch:
27 mm
Awg Gauge:
AWG 6...AWG 2/0 fine stranded aluminium/copper || AWG 14...AWG 3/0 rigid or stranded aluminium/copper
9 Mm Pitches:
12
Mounting Mode:
clip-on 35 x 15 mm symmetrical DIN rail) || by screws plate)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Local Signalling:
presence of auxiliary contacts flag green)
Ik Degree Of Protection:
IK07 IEC 62262
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Tightening Torque:
5-5 N.m 2.5-16 mm² (AWG 14...AWG 4) || 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Poles Description:
4P
Pvc Free:
Yes
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Standards:
NMX J-266 || CSA C22.2 No 5 || GB 14048.2 || UL 489 || NEMA AB1 || EN/IEC 60947-2 || EN/IEC 60947-5-1
Environmental Disclosure:
ENVPEP1610005EN
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric BDL46030 Molded Case Circuit Brkr 600Y/347V 30A
  • Schneider Electric BDL46030 Molded Case Circuit Brkr 600Y/347V 30A
  • Schneider Electric BDL46030 Molded Case Circuit Brkr 600Y/347V 30A
$1,465.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600Y/347VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. This circuit breaker's unit mount construction features traditional back pan mounting with screws or integrated DIN rail mounting for installation flexibility. This unit features EverLink lugs, a patented design to reduce loosening of cables over time, on both termination ends. This PowerPacT B, 30A, 4 pole, circuit breaker has a breaking capacity of 14kA at 600Y/347VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose