Schneider Electric BGA24050Y1 Molded Case Circuit Brkr 480Y/277V 50A

(No reviews yet) Write a Review
SKU:
BGA24050Y1
UPC:
785901457893
Condition:
New
Tightening Torque:
3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
[Ue] Rated Operational Voltage:
525 V AC 50/60 Hz UL 489
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Local Signalling:
presence of auxiliary contacts flag green)
Breaking Capacity:
65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 18 kA 600Y/347 V AC 50/60 Hz UL 489
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
9 Mm Pitches:
6
Utilisation Category:
category A
Range:
PowerPact
Number Of Slots:
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Control Type:
toggle
Poles Description:
2P
Eu Rohs Directive:
Compliant with Exemptions
Product Or Component Type:
circuit breaker
Depth:
89 mm
Mounting Height:
76.2 mm
Ik Degree Of Protection:
IK07 IEC 62262
Trip Unit Technology:
thermal-magnetic
Pvc Free:
Yes
Circuit Breaker Application:
HACR rated
Network Frequency:
50/60 Hz
Continuous Current Rating:
0.8
Wire Stripping Length:
20 mm
Product Name:
PowerPact B
Width:
54 mm
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Phase Connection:
AB
Mechanical Durability:
20000 cycles IEC 947-1 Annex K ed 5.2
Environmental Disclosure:
ENVPEP1610005EN
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Height:
137 mm
[Ics] Rated Service Breaking Capacity:
65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Color:
Gray RAL 7016)
Electrical Connection:
I-Line connection, line || lugs, load
Net Weight:
0.952 kg
Halogen Content Performance:
Halogen free product
Ip Degree Of Protection:
front cover IP40 IEC 60529
Rohs Exemption Information:
Yes
Device Application:
distribution
Breaking Capacity Code:
G
Pollution Degree:
3 IEC 60947-1
Quantity Per Set:
set of 1
Standards:
NMX J-266 || UL 489 || GB 14048.2 || EN/IEC 60947-5-1 || NEMA AB1 || EN/IEC 60947-2 || CSA C22.2 No 5
Ambient Air Temperature For Storage:
-50-85 °C
Device Short Name:
BG 050
Mounting Mode:
I-Line
Suitability For Isolation:
yes IEC 60947-2
Sustainable Offer Status:
Green Premium product
Line Rated Current:
50-50 A
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Quality Labels:
CE
Ambient Air Temperature For Operation:
-25-70 °C
Awg Gauge:
AWG 14...AWG 2/0 aluminium/copper
Circularity Profile:
N/A
Connection Pitch:
27 mm
  • Schneider Electric BGA24050Y1 Molded Case Circuit Brkr 480Y/277V 50A
  • Schneider Electric BGA24050Y1 Molded Case Circuit Brkr 480Y/277V 50A
  • Schneider Electric BGA24050Y1 Molded Case Circuit Brkr 480Y/277V 50A
$964.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 35kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 50A, 2 pole, circuit breaker has a breaking capacity of 35kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose