Schneider Electric BGL36090LU Molded Case Circuit Brkr 600Y/347V 90A

(No reviews yet) Write a Review
SKU:
BGL36090LU
UPC:
3606481149466
Condition:
New
[Ue] Rated Operational Voltage:
525 V AC 50/60 Hz UL 489
Ip Degree Of Protection:
front cover IP40 IEC 60529
Control Type:
toggle
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Suitability For Isolation:
yes IEC 60947-2
Local Signalling:
presence of auxiliary contacts flag green)
Circularity Profile:
N/A
Height:
137 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Line Rated Current:
90-90 A
Electrical Connection:
Everlink lug, line || Everlink lug, load
[Ics] Rated Service Breaking Capacity:
65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Color:
Gray RAL 7016)
Number Of Slots:
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
Product Name:
PowerPact B
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Net Weight:
1.074 kg
Sustainable Offer Status:
Green Premium product
Depth:
80 mm
Mounting Mode:
clip-on 35 mm symmetrical DIN rail) || by screws plate)
Utilisation Category:
category A
Pvc Free:
Yes
Poles Description:
3P
Ambient Air Temperature For Operation:
-25-70 °C
Environmental Disclosure:
ENVPEP1610005EN
Width:
81 mm
Rohs Exemption Information:
Yes
Quantity Per Set:
set of 1
Wire Stripping Length:
20 mm
Eu Rohs Directive:
Compliant with Exemptions
Trip Unit Technology:
thermal-magneticTM-D,
Continuous Current Rating:
0.8
Breaking Capacity Code:
G
Awg Gauge:
AWG 6...AWG 2/0 fine stranded aluminium/copper || AWG 14...AWG 3/0 rigid or stranded aluminium/copper
Standards:
GB 14048.2 || EN/IEC 60947-2 || UL 489 || EN/IEC 60947-5-1 || NMX J-266 || CSA C22.2 No 5 || NEMA AB1
Device Application:
distribution
Trip Unit Name:
TM-D
Quality Labels:
CE
Network Frequency:
50/60 Hz
Halogen Content Performance:
Halogen free product
Breaking Capacity:
65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 18 kA 600Y/347 V AC 50/60 Hz UL 489
Connection Pitch:
27 mm
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Range:
PowerPact
Mechanical Durability:
15000 cycles IEC 947-1 Annex K ed 5.2
Tightening Torque:
5-5 N.m 2.5-16 mm² (AWG 14...AWG 4) || 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
Product Or Component Type:
circuit breaker
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
California Proposition 65:
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Protected Poles Description:
3t
Circuit Breaker Application:
HACR rated
Device Short Name:
BG 090
9 Mm Pitches:
9
Ik Degree Of Protection:
IK07 IEC 62262
Pollution Degree:
3 IEC 60947-1
Ambient Air Temperature For Storage:
-50-85 °C
Mercury Free:
Yes
Operating Altitude:
6561.68 ft (2000 m) without derating || 5000 m with derating
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric BGL36090LU Molded Case Circuit Brkr 600Y/347V 90A
  • Schneider Electric BGL36090LU Molded Case Circuit Brkr 600Y/347V 90A
  • Schneider Electric BGL36090LU Molded Case Circuit Brkr 600Y/347V 90A
$1,642.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600Y/347VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. This circuit breaker's unit mount construction features traditional back pan mounting with screws or integrated DIN rail mounting for installation flexibility. This unit features EverLink lugs, a patented design to reduce loosening of cables over time, on both termination ends. This PowerPacT B, 90A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600Y/347VAC. This circuit breaker has a continuous current rating of 80%. This unit includes a control wire terminal on the line end EverLink lug. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. EverLink lugs are also available with unique integrated control wire terminals.
View AllClose