1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
Ambient Air Temperature For Operation:
-25-70 °C
Continuous Current Rating:
0.8
Pollution Degree:
3 IEC 60947-1
Breaking Capacity:
100 kA 208Y/120 V AC 50/60 Hz UL 489 || 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480/277 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600Y/347 V AC 50/60 Hz UL 489 || 50 kA 250 V DC UL 489
Height:
137 mm
Depth:
80 mm
Standards:
NMX J-266 || CSA C22.2 No 5 || EN/IEC 60947-2 || NEMA AB1 || EN/IEC 60947-5-1 || UL 489 || GB 14048.2
Color:
Gray RAL 7016)
Protected Poles Description:
3t
Ambient Air Temperature For Storage:
-50-85 °C
Range:
PowerPact
Circuit Breaker Application:
HACR rated
Circularity Profile:
N/A
Trip Unit Technology:
thermal-magneticTM-D,
Poles Description:
3P
Local Signalling:
presence of auxiliary contacts flag green)
Mechanical Durability:
15000 cycles IEC 947-1 Annex K ed 5.2
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Electrical Connection:
terminal nut, ON and OFF end
Trip Unit Name:
TM-D
Operating Altitude:
6561.68 ft (2000 m) without derating || 5000 m with derating
Mounting Mode:
clip-on 35 mm symmetrical DIN rail) || by screws plate)
100 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 25 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 2.5 kA 690 V AC 50/60 Hz IEC 60947-2 || 65 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 65 kA 440 V AC 50/60 Hz IEC 60947-2
Environmental Disclosure:
ENVPEP1610005EN
Quantity Per Set:
set of 1
Ip Degree Of Protection:
front cover IP40 IEC 60529
Sustainable Offer Status:
Green Premium product
Pvc Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Device Application:
distribution
Breaking Capacity Code:
J
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz UL 489
Wire Stripping Length:
20 mm
Rohs Exemption Information:
Yes
Net Weight:
0.924 kg
Ik Degree Of Protection:
IK07 IEC 62262
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Product Or Component Type:
circuit breaker
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker...
PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker...
PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker...
PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker...