Schneider Electric GV2RT06 Gv2 Motor Cb High Inrush 1-1.6A Toggle

(No reviews yet) Write a Review
SKU:
GV2RT06
UPC:
3389110520620
Condition:
New
Device Short Name:
GV2RT
Mechanical Durability:
100000 cycles
Depth:
78.5 mm
[Ith] Conventional Free Air Thermal Current:
1.6 A IEC 60947-4-1
Rated Duty:
continuous IEC 60947-4-1
Product Certifications:
CCC || UL || CSA || EAC || LROS (Lloyds register of shipping) || BV || UKCA
Eu Rohs Directive:
Compliant with Exemptions
Line Rated Current:
1.6 A
Width:
45 mm
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1 || AC-3e IEC 60947-4-1
Network Type:
AC
Magnetic Tripping Current:
33-33 A
Trip Unit Technology:
thermal-magnetic
Fixing Mode:
35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
Device Application:
motor protection || motor
California Proposition 65:
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Environmental Disclosure:
ENVPEP121004
Warranty:
18 months
Circularity Profile:
ENVEOLI121004
Rohs Exemption Information:
Yes
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Network Frequency:
50/60 Hz IEC 60947-4-1
Fire Resistance:
960 °C IEC 60695-2-11
Sustainable Offer Status:
Green Premium product
Motor Power Kw:
0.18-0.18 kW 220/230 V AC 50/60 Hz motor protection high peak current || 0.25-0.25 kW 220/230 V AC 50/60 Hz motor protection high peak current || 0.37-0.37 kW 400/415 V AC 50/60 Hz motor protection high peak current || 0.55-0.55 kW 400/415 V AC 50/60
Ambient Air Temperature For Storage:
-40-80 °C
Ik Degree Of Protection:
IK04
Tightening Torque:
1.7 N.m screw clamp terminal
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ip Degree Of Protection:
IP20 IEC 60529
Breaking Capacity:
100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ui] Rated Insulation Voltage:
690 V AC 50/60 Hz IEC 60947-2
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2
Control Type:
toggle
Electrical Durability:
100000 cycles AC-3 415 V In || 100000 cycles AC-3e 415 V In
Ambient Air Temperature For Operation:
-20-60 °C
Thermal Protection Adjustment Range:
1-1.6 A IEC 60947-4-1
Product Name:
TeSys GV2 || TeSys Deca
Suitability For Isolation:
yes IEC 60947-1 § 7-1-6
Mechanical Robustness:
shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
Climatic Withstand:
IACS E10
Poles Description:
3P
Range:
TeSys Deca
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-2
Height:
89 mm
Power Dissipation Per Pole:
2.5 W
Standards:
EN/IEC 60947-2 || EN/IEC 60947-4-1
Mercury Free:
Yes
Product Or Component Type:
motor circuit breaker
Operating Altitude:
6561.68 ft (2000 m)
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Catalog:
View
Datasheet:
View
$180.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 1.6A/690V, for high starting current peak motor applications 0.37-0.55kW@400V. It provides a thermal-magnetic protection with a thermal setting range 1-1.6A, a magnetic tripping level at 20xIn, high breaking capacity Icu 100kA. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. It can be used for protection of 3-phase transformer applications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose