Schneider Electric GV4PB03S Motbreakgv4Pbul489Th/Mag 3.5A 100Kaelink

(No reviews yet) Write a Review
SKU:
GV4PB03S
UPC:
3606489868642
Condition:
New
Circularity Profile:
ENVEOLI1704004EN
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Phase Failure Sensitivity:
yes IEC 60947-4-1
Breaking Capacity:
100 kA SCCR 240 V AC 60 Hz UL 489 || 65 kA SCCR 480Y/277 V AC 60 Hz UL 489 || 25 kA SCCR 600Y/347 V AC 60 Hz UL 489 || 120 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 609
[Ics] Rated Service Short-Circuit Breaking Capacity:
100 % 220/240 V AC 50/60 Hz IEC 60947-2 || 100 % 380/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 525 V AC 50/60 Hz IEC 60947-2 || 25 % 660/690 V AC 50/60 Hz IEC 60947-2
Product Name:
TeSys GV4 || TeSys Deca
Color:
Gray RAL 7016)
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Device Short Name:
GV4PB
Warranty:
18 months
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2 || 600Y/347 V AC 60 Hz UL 489
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Standards:
EN/IEC 60947-1 || EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 489 || CSA C22.2 No 5
Range:
TeSys Deca
Halogen Content Performance:
Halogen free plastic parts product
Operating Position:
any position
Rated Duty:
continuous IEC 60947-4-1
Pvc Free:
Yes
Device Application:
motor protection
Mechanical Durability:
40000 cycles
Trip Unit Technology:
electronic || thermal-magnetic
Sustainable Offer Status:
Green Premium product
Fire Resistance:
960 °C IEC 60695-2-11
Width:
81 mm
Net Weight:
1.45 kg
Ambient Air Temperature For Operation:
-25-70 °C
Product Or Component Type:
motor circuit breaker
Power Dissipation Per Pole:
4.6 W
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Connections - Terminals:
EverLink BTR screw connectors top) 1 1.5-70 mm² - rigid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - rigid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
Control Type:
toggle
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Eu Rohs Directive:
Compliant with Exemptions
Pollution Degree:
3
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Line Rated Current:
3.5 A
Mercury Free:
Yes
Rohs Exemption Information:
Yes
Depth:
116 mm
Magnetic Tripping Current:
60-60 A
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Height:
171 mm
Ip Degree Of Protection:
IP40 IEC 60529
Product Certifications:
IEC || UL || CSA
Poles Description:
3P
Suitability For Isolation:
yes IEC 60947-1
Electrical Durability:
40000 cycles AC-3 440 V In/2 || 40000 cycles AC-3 440 V In
Climatic Withstand:
IACS E10
Maximum Operating Rate:
25 cyc/h
Environmental Disclosure:
ENVPEP1704004EN
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Range Of Product:
TeSys GV4
Ambient Air Temperature For Storage:
-50-85 °C
Ik Degree Of Protection:
IK07 IEC 62262
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Operating Altitude:
5000 m
Datasheet:
View
$508.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 3.5A/690V, for protection of 3-phase motors 0.55-1.5kW@400V. Multifunction circuit breaker UL489 compliant, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 1.4-3.5A, a selectable tripping class 10 or 20, rated tripping current 125%, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL 489, CSA C22.2 N°5), Green Premium compliant (RoHS/REACh).