Schneider Electric

Schneider Electric GV4PB25S Motbreakgv4Pbul489Th/Mag 25A 100Ka Elink

(No reviews yet) Write a Review
SKU:
GV4PB25S
UPC:
3.60649E+12
Condition:
New
Sustainable Offer Status:
Green Premium product
Trip Unit Technology:
thermal-magnetic || electronic
Power Dissipation Per Pole:
4.6 W
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Line Rated Current:
25 A
Product Certifications:
IEC || UL || CSA
Depth:
116 mm
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Magnetic Tripping Current:
425-425 A
Operating Altitude:
5000 m
Connections - Terminals:
EverLink BTR screw connectors top) 1 1.5-70 mm² - rigid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - rigid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
Device Short Name:
GV4PB
Range:
TeSys Deca
Warranty:
18 months
Net Weight:
1.45 kg
Product Or Component Type:
motor circuit breaker
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2 || 600Y/347 V AC 60 Hz UL 489
Ip Degree Of Protection:
IP40 IEC 60529
Device Application:
motor protection
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Maximum Operating Rate:
25 cyc/h
Environmental Disclosure:
ENVPEP1704004EN
Operating Position:
any position
Rated Duty:
continuous IEC 60947-4-1
Height:
171 mm
Mercury Free:
Yes
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Ik Degree Of Protection:
IK07 IEC 62262
Fire Resistance:
960 °C IEC 60695-2-11
Halogen Content Performance:
Halogen free plastic parts product
Pvc Free:
Yes
Electrical Durability:
40000 cycles AC-3 440 V In/2 || 20000 cycles AC-3 440 V In
Climatic Withstand:
IACS E10
Breaking Capacity:
100 kA SCCR 240 V AC 60 Hz UL 489 || 65 kA SCCR 480Y/277 V AC 60 Hz UL 489 || 25 kA SCCR 600Y/347 V AC 60 Hz UL 489 || 120 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 609
Rohs Exemption Information:
Yes
Product Name:
TeSys GV4 || TeSys Deca
[Ics] Rated Service Short-Circuit Breaking Capacity:
100 % 220/240 V AC 50/60 Hz IEC 60947-2 || 100 % 380/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 525 V AC 50/60 Hz IEC 60947-2 || 25 % 660/690 V AC 50/60 Hz IEC 60947-2
Poles Description:
3P
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Suitability For Isolation:
yes IEC 60947-1
Range Of Product:
TeSys GV4
Control Type:
toggle
Phase Failure Sensitivity:
yes IEC 60947-4-1
Ambient Air Temperature For Storage:
-50-85 °C
Color:
Gray RAL 7016)
Width:
81 mm
Eu Rohs Directive:
Compliant with Exemptions
Ambient Air Temperature For Operation:
-25-70 °C
Circularity Profile:
ENVEOLI1704004EN
Standards:
EN/IEC 60947-1 || EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 489 || CSA C22.2 No 5
Pollution Degree:
3
Mechanical Durability:
40000 cycles
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Datasheet:
View
$551.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 25A/690V, for protection of 3-phase motors 5.5-11kW@400V. Multifunction circuit breaker UL489 compliant, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 10-25A, a selectable tripping class 10 or 20, rated tripping current 125%, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL 489, CSA C22.2 N°5), Green Premium compliant (RoHS/REACh).
View AllClose