Schneider Electric HDA260201 Molded Case Circuit Breaker 600V 20A

(No reviews yet) Write a Review
SKU:
HDA260201
UPC:
7.85901E+11
Condition:
New
Communication Interface:
Modbus || Ethernet
Circuit Breaker Application:
HACR rated
Quality Labels:
CE
Protected Poles Description:
2t
Utilisation Category:
category A
Network Frequency:
50/60 Hz
Pvc Free:
Yes
Depth:
86 mm
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Line Rated Current:
20-20 A
Net Weight:
2.2 kg
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Product Name:
PowerPact H
Terminal Identifier:
AL150HD
Eu Rohs Directive:
Compliant with Exemptions
Device Application:
distribution
Breaking Capacity Code:
D
Circularity Profile:
ENVEOLI2206027EN
Local Signalling:
switched off (OFF) 1 trip indicator green)
Product Or Component Type:
circuit breaker
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Continuous Current Rating:
0.8
Trip Unit Technology:
thermal-magnetic
Color:
Black
Mercury Free:
Yes
Phase Connection:
AB
Suitability For Isolation:
yes IEC 60947-2
Magnetic Tripping Current:
750-750 A
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Environmental Disclosure:
ENVPEP2206027EN
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Width:
104 mm
Pollution Degree:
3 IEC 60947-1
Ambient Air Temperature For Storage:
-50-85 °C
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Height:
163 mm
Poles Description:
2P
Mounting Height:
3 in
Magnetic Hold Current:
350 A
Mounting Support:
bracket
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Electrical Connection:
I-Line connection, line || lugs, load
Ambient Air Temperature For Operation:
-2-70 °C
Wire Stripping Length:
16 mm
Control Type:
toggle
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Quantity Per Set:
1
Range:
PowerPact
Ip Degree Of Protection:
front cover IP40 IEC 60529
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Sustainable Offer Status:
Green Premium product
Product Certifications:
UL || CSA || NOM
Mounting Mode:
I-Line bracket)
Rohs Exemption Information:
Yes
Warranty:
18 months
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
  • Schneider Electric HDA260201 Molded Case Circuit Breaker 600V 20A
  • Schneider Electric HDA260201 Molded Case Circuit Breaker 600V 20A
$899.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 20A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.