Schneider Electric HDA260301 Molded Case Circuit Breaker 600V 30A
Schneider Electric
$899.00
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 30A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Width:
- 104 mm
- Terminal Identifier:
- AL150HD
- Line Rated Current:
- 30-30 A
- Wire Stripping Length:
- 16 mm
- Network Frequency:
- 50/60 Hz
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Control Type:
- toggle
- Ambient Air Temperature For Operation:
- -2-70 °C
- Depth:
- 86 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Protected Poles Description:
- 2t
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Circularity Profile:
- ENVEOLI2206027EN
- Net Weight:
- 2.2 kg
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Or Component Type:
- circuit breaker
- Quantity Per Set:
- 1
- Pollution Degree:
- 3 IEC 60947-1
- Phase Connection:
- AB
- Color:
- Black
- Environmental Disclosure:
- ENVPEP2206027EN
- Electrical Connection:
- I-Line connection, line || lugs, load
- Warranty:
- 18 months
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Height:
- 3 in
- Device Application:
- distribution
- Range:
- PowerPact
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Mounting Support:
- bracket
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Poles Description:
- 2P
- Product Name:
- PowerPact H
- Trip Unit Technology:
- thermal-magnetic
- Suitability For Isolation:
- yes IEC 60947-2
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Continuous Current Rating:
- 0.8
- Mounting Mode:
- I-Line bracket)
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Magnetic Tripping Current:
- 750-750 A
- Product Certifications:
- UL || CSA || NOM
- Pvc Free:
- Yes
- Magnetic Hold Current:
- 350 A
- Communication Interface:
- Modbus || Ethernet
- Rohs Exemption Information:
- Yes
- Utilisation Category:
- category A
- Height:
- 163 mm
- Sustainable Offer Status:
- Green Premium product
- Quality Labels:
- CE
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity Code:
- D
- Eu Rohs Directive:
- Compliant with Exemptions
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Mercury Free:
- Yes
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View