Schneider Electric HDA260401 Molded Case Circuit Breaker 600V 40A

(No reviews yet) Write a Review
SKU:
HDA260401
UPC:
7.85901E+11
Condition:
New
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Quantity Per Set:
1
Magnetic Tripping Current:
850-850 A
Device Application:
distribution
Circularity Profile:
ENVEOLI2206027EN
Suitability For Isolation:
yes IEC 60947-2
Warranty:
18 months
Electrical Connection:
I-Line connection, line || lugs, load
Breaking Capacity Code:
D
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Poles Description:
2P
Magnetic Hold Current:
400 A
Mercury Free:
Yes
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Environmental Disclosure:
ENVPEP2206027EN
Pvc Free:
Yes
Utilisation Category:
category A
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Product Or Component Type:
circuit breaker
Range:
PowerPact
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Pollution Degree:
3 IEC 60947-1
Wire Stripping Length:
16 mm
Sustainable Offer Status:
Green Premium product
Network Frequency:
50/60 Hz
Protected Poles Description:
2t
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Mounting Mode:
I-Line bracket)
Continuous Current Rating:
0.8
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Width:
104 mm
Mounting Support:
bracket
Product Name:
PowerPact H
Product Certifications:
UL || CSA || NOM
Rohs Exemption Information:
Yes
Terminal Identifier:
AL150HD
Local Signalling:
switched off (OFF) 1 trip indicator green)
Phase Connection:
AB
Trip Unit Technology:
thermal-magnetic
Ip Degree Of Protection:
front cover IP40 IEC 60529
Depth:
86 mm
Color:
Black
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Ambient Air Temperature For Storage:
-50-85 °C
Line Rated Current:
40-40 A
Control Type:
toggle
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Communication Interface:
Modbus || Ethernet
Height:
163 mm
Ambient Air Temperature For Operation:
-2-70 °C
Circuit Breaker Application:
HACR rated
Net Weight:
2.2 kg
Quality Labels:
CE
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Mounting Height:
3 in
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric HDA260401 Molded Case Circuit Breaker 600V 40A
  • Schneider Electric HDA260401 Molded Case Circuit Breaker 600V 40A
$899.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 40A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.