Schneider Electric HDA36150U33X Molded Case Circuit Breaker 600V 150A
Schneider Electric
$3,107.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Standard with a 3.2S trip unit and an LSI function with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 150A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2 S, LSI
- Continuous Current Rating:
- 0.8
- Suitability For Isolation:
- yes IEC 60947-2
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Device Application:
- distribution
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Circularity Profile:
- ENVEOLI2206028EN
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Pvc Free:
- Yes
- Warranty:
- 18 months
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Sustainable Offer Status:
- Green Premium product
- Rohs Exemption Information:
- Yes
- Quality Labels:
- CE
- Poles Description:
- 3P
- Trip Unit Name:
- MicroLogic 3.2 S
- Environmental Disclosure:
- ENVPEP2206028EN
- Wire Stripping Length:
- 16 mm
- Network Frequency:
- 50/60 Hz
- Net Weight:
- 2.2 kg
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Electrical Connection:
- I-Line connection, line || lugs, load
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Height:
- 163 mm
- Phase Connection:
- ABC
- Quantity Per Set:
- 1
- Breaking Capacity Code:
- D
- Product Name:
- PowerPact H
- Product Or Component Type:
- circuit breaker
- Depth:
- 86 mm
- Product Certifications:
- UL || CSA || NOM
- Control Type:
- toggle
- Ambient Air Temperature For Storage:
- -50-85 °C
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Range:
- PowerPact
- Mounting Support:
- bracket
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Line Rated Current:
- 150-150 A
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Utilisation Category:
- category A
- Mounting Height:
- 4.5 in
- Width:
- 104 mm
- Terminal Identifier:
- AL150HD
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mounting Mode:
- I-Line bracket)
- Communication Interface:
- Modbus || Ethernet
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Eu Rohs Directive:
- Compliant with Exemptions
- Circuit Breaker Application:
- HACR rated
- Protected Poles Description:
- 3t
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mercury Free:
- Yes
- Color:
- Black
- Pollution Degree:
- 3 IEC 60947-1
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View