Schneider Electric HDL36015 Molded Case Circuit Breaker 600V 15A
Schneider Electric
$1,088.00
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 15A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Poles Description:
- 3P
- Utilisation Category:
- category A
- Color:
- Black
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Wire Stripping Length:
- 16 mm
- Warranty:
- 18 months
- Line Rated Current:
- 15-15 A
- Circuit Breaker Application:
- HACR rated
- Protected Poles Description:
- 3t
- Mounting Support:
- lug
- Mercury Free:
- Yes
- Mounting Mode:
- unit mount lug)
- Control Type:
- toggle
- Magnetic Hold Current:
- 350 A
- Device Application:
- distribution
- Product Name:
- PowerPact H
- Product Certifications:
- UL || CSA || NOM
- Rohs Exemption Information:
- Yes
- Quality Labels:
- CE
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Height:
- 163 mm
- Circularity Profile:
- ENVEOLI2206027EN
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Pvc Free:
- Yes
- Range:
- PowerPact
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Or Component Type:
- circuit breaker
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206027EN
- Width:
- 104 mm
- Breaking Capacity Code:
- D
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Suitability For Isolation:
- yes IEC 60947-2
- Magnetic Tripping Current:
- 750-750 A
- Trip Unit Technology:
- thermal-magnetic
- Network Frequency:
- 50/60 Hz
- Pollution Degree:
- 3 IEC 60947-1
- Quantity Per Set:
- 1
- Continuous Current Rating:
- 0.8
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Terminal Identifier:
- AL150HD
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Sustainable Offer Status:
- Green Premium product
- Ambient Air Temperature For Operation:
- -2-70 °C
- Depth:
- 86 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Storage:
- -50-85 °C
- Eu Rohs Directive:
- Compliant with Exemptions
- Net Weight:
- 2.2 kg
- Electrical Connection:
- lugs, line || lugs, load
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View