- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Mounting Mode:
- unit mount lug)
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection:
- lugs, line || lugs, load
- Width:
- 104 mm
- Communication Interface:
- Modbus || Ethernet
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Breaking Capacity Code:
- D
- Height:
- 163 mm
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Control Type:
- toggle
- Device Application:
- distribution
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Protected Poles Description:
- 3t
- Color:
- Black
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 5.2 A, LSI
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Product Name:
- PowerPact H
- Warranty:
- 18 months
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Sustainable Offer Status:
- Green Premium product
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Line Rated Current:
- 60-60 A
- Mounting Support:
- lug
- Circuit Breaker Application:
- HACR rated
- Mercury Free:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Quantity Per Set:
- 1
- Utilisation Category:
- category A
- Range:
- PowerPact
- Suitability For Isolation:
- yes IEC 60947-2
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Operation:
- -2-70 °C
- Wire Stripping Length:
- 16 mm
- Terminal Identifier:
- AL150HD
- Trip Unit Name:
- MicroLogic 5.2 A
- Depth:
- 86 mm
- Product Or Component Type:
- circuit breaker
- Network Frequency:
- 50/60 Hz
- Product Certifications:
- UL || CSA || NOM
- Circularity Profile:
- ENVEOLI2206028EN
- Poles Description:
- 3P
- Pvc Free:
- Yes
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Continuous Current Rating:
- 0.8
- Rohs Exemption Information:
- Yes
- Net Weight:
- 2.2 kg
- Environmental Disclosure:
- ENVPEP2206028EN
- Quality Labels:
- CE