Schneider Electric HGA260305 Molded Case Circuit Breaker 600V 30A

(No reviews yet) Write a Review
SKU:
HGA260305
UPC:
785901834120
Condition:
New
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Width:
104 mm
Depth:
86 mm
Magnetic Hold Current:
350 A
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Electrical Connection:
I-Line connection, line || lugs, load
Pvc Free:
Yes
Mounting Height:
3 in
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Phase Connection:
CA
Circularity Profile:
ENVEOLI1311006EN
Rohs Exemption Information:
Yes
Height:
163 mm
Eu Rohs Directive:
Compliant
Product Name:
PowerPact H
Communication Interface:
Modbus || Ethernet
Wire Stripping Length:
16 mm
Net Weight:
2.2 kg
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mounting Mode:
I-Line bracket)
Magnetic Tripping Current:
750-750 A
Mounting Support:
bracket
Protected Poles Description:
2t
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Environmental Disclosure:
ENVPEP1311006EN
Network Frequency:
50/60 Hz
Color:
Black
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Range:
PowerPact
Circuit Breaker Application:
HACR rated
Line Rated Current:
30-30 A
Terminal Identifier:
AL150HD
Local Signalling:
switched off (OFF) 1 trip indicator green)
Control Type:
toggle
Poles Description:
2P
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Ambient Air Temperature For Operation:
-2-70 °C
Utilisation Category:
category A
Warranty:
18 months
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Suitability For Isolation:
yes IEC 60947-2
Quality Labels:
CE
Continuous Current Rating:
0.8
Pollution Degree:
3 IEC 60947-1
Trip Unit Technology:
thermal-magnetic
Breaking Capacity Code:
G
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Sustainable Offer Status:
Green Premium product
Device Application:
distribution
Ambient Air Temperature For Storage:
-50-85 °C
Product Certifications:
UL || CSA || NOM
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ip Degree Of Protection:
front cover IP40 IEC 60529
Quantity Per Set:
1
Product Or Component Type:
circuit breaker
Brochure:
View
Catalog:
View
Datasheet:
View
$2,007.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 30A, 2 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with a CA phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose