Local Signalling:
switched off (OFF) 1 trip indicator green)
Control Type:
toggle
Ambient Air Temperature For Storage:
-50-85 °C
Environmental Disclosure:
ENVPEP2206027EN
Net Weight:
2.2 kg
Protected Poles Description:
2t
Device Application:
distribution
Color:
Black
Ip Degree Of Protection:
front cover IP40 IEC 60529
Mercury Free:
Yes
Suitability For Isolation:
yes IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Depth:
86 mm
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Magnetic Hold Current:
400 A
Rohs Exemption Information:
Yes
Ambient Air Temperature For Operation:
-2-70 °C
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Communication Interface:
Modbus || Ethernet
Mounting Mode:
I-Line bracket)
Product Or Component Type:
circuit breaker
Pollution Degree:
3 IEC 60947-1
Product Certifications:
UL || CSA || NOM
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Quality Labels:
CE
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Poles Description:
2P
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Width:
104 mm
Pvc Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile:
ENVEOLI2206027EN
Eu Rohs Directive:
Compliant with Exemptions
Phase Connection:
BC
Network Frequency:
50/60 Hz
Sustainable Offer Status:
Green Premium product
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Wire Stripping Length:
16 mm
Range:
PowerPact
Circuit Breaker Application:
HACR rated
Height:
163 mm
Line Rated Current:
40-40 A
Magnetic Tripping Current:
850-850 A
Product Name:
PowerPact H
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Quantity Per Set:
1
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Utilisation Category:
category A
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Continuous Current Rating:
0.8
Mounting Height:
3 in
Warranty:
18 months
Mounting Support:
bracket
Terminal Identifier:
AL150HD
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Breaking Capacity Code:
G
Trip Unit Technology:
thermal-magnetic
Electrical Connection:
I-Line connection, line || lugs, load
  • Schneider Electric HGA260404 Molded Case Circuit Breaker 600V 40A
  • Schneider Electric HGA260404 Molded Case Circuit Breaker 600V 40A
$3,010.50

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 40A, 2 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with a BC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.