Schneider Electric

Schneider Electric HGA36125YP Molded Case Circuit Breaker 600V 125A

(No reviews yet) Write a Review
SKU:
HGA36125YP
UPC:
3606486118290
Condition:
New
Continuous Current Rating:
0.8
Network Frequency:
50/60 Hz
Magnetic Hold Current:
900 A
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Quality Labels:
CE
Pvc Free:
Yes
Width:
104 mm
Utilisation Category:
category A
Sustainable Offer Status:
Green Premium product
Magnetic Tripping Current:
1700-1700 A
Control Type:
toggle
Product Certifications:
UL || CSA || NOM
Breaking Capacity Code:
G
Net Weight:
2.2 kg
Mercury Free:
Yes
Ip Degree Of Protection:
front cover IP40 IEC 60529
Color:
Black
Protected Poles Description:
3t
Height:
163 mm
Communication Interface:
Modbus || Ethernet
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Quantity Per Set:
1
Circuit Breaker Application:
HACR rated
Suitability For Isolation:
yes IEC 60947-2
Range:
PowerPact
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Line Rated Current:
125-125 A
Warranty:
18 months
Electrical Connection:
I-Line connection, line || lugs, load
Trip Unit Technology:
thermal-magnetic
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ambient Air Temperature For Operation:
-2-70 °C
Pollution Degree:
3 IEC 60947-1
Accessory / Separate Part Type:
padlocking device
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Rohs Exemption Information:
Yes
Wire Stripping Length:
16 mm
Mounting Mode:
I-Line bracket)
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Mounting Support:
bracket
Terminal Identifier:
AL150HD
Poles Description:
3P
Ambient Air Temperature For Storage:
-50-85 °C
Mounting Height:
4.5 in
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Product Or Component Type:
circuit breaker
Device Application:
distribution
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Local Signalling:
switched off (OFF) 1 trip indicator green)
Environmental Disclosure:
ENVPEP1311006EN
Phase Connection:
ABC
Depth:
86 mm
Eu Rohs Directive:
Compliant
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Product Name:
PowerPact H
Circularity Profile:
ENVEOLI1311006EN
Brochure:
View
Catalog:
View
Datasheet:
View
$8,676.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 125A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. This unit includes a factory installed padlock handle. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose