Schneider Electric HGL36035 Molded Case Circuit Breaker 600V 35A

(No reviews yet) Write a Review
SKU:
HGL36035
UPC:
785901598732
Condition:
New
Ip Degree Of Protection:
front cover IP40 IEC 60529
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Color:
Black
Circularity Profile:
ENVEOLI2206027EN
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Pollution Degree:
3 IEC 60947-1
Range:
PowerPact
Communication Interface:
Modbus || Ethernet
Poles Description:
3P
Rohs Exemption Information:
Yes
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Network Frequency:
50/60 Hz
Device Application:
distribution
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Terminal Identifier:
AL150HD
Electrical Connection:
lugs, line || lugs, load
Quality Labels:
CE
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Trip Unit Technology:
thermal-magnetic
Pvc Free:
Yes
Suitability For Isolation:
yes IEC 60947-2
Quantity Per Set:
1
Magnetic Hold Current:
400 A
Mercury Free:
Yes
Control Type:
toggle
Continuous Current Rating:
0.8
Circuit Breaker Application:
HACR rated
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Height:
163 mm
Mounting Mode:
unit mount lug)
Mounting Support:
lug
Net Weight:
2.2 kg
Ambient Air Temperature For Operation:
-2-70 °C
Environmental Disclosure:
ENVPEP2206027EN
Wire Stripping Length:
16 mm
Warranty:
18 months
Depth:
86 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Breaking Capacity Code:
G
Eu Rohs Directive:
Compliant with Exemptions
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Sustainable Offer Status:
Green Premium product
Protected Poles Description:
3t
Magnetic Tripping Current:
850-850 A
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Width:
104 mm
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Product Name:
PowerPact H
Product Or Component Type:
circuit breaker
Product Certifications:
UL || CSA || NOM
Ambient Air Temperature For Storage:
-50-85 °C
Utilisation Category:
category A
Local Signalling:
switched off (OFF) 1 trip indicator green)
Line Rated Current:
35-35 A
Brochure:
View
Catalog:
View
Datasheet:
View
$1,493.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 35A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.