Schneider Electric JDL34250WU31X Molded Case Circuit Breaker 480V 250A
Schneider Electric
$3,489.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides Micrologic Standard with a 3.2 trip unit and an LI function with a breaking capacity of 18kA at 480VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 18kA at 480VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Mounting Support:
- lug
- Product Or Component Type:
- circuit breaker
- Network Frequency:
- 50/60 Hz
- Circuit Breaker Application:
- HACR rated
- Pvc Free:
- Yes
- Terminal Identifier:
- AL250JD
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Wire Stripping Length:
- 25 mm
- Sustainable Offer Status:
- Green Premium product
- Rohs Exemption Information:
- Yes
- Product Name:
- PowerPact J
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- [Ue] Rated Operational Voltage:
- 480/277 V AC 50/60 Hz IEC 60947-3
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Pollution Degree:
- 3 IEC 60947-1
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Protection Type:
- overload protection || short-circuit protection
- Width:
- 104 mm
- Height:
- 191 mm
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Trip Unit Name:
- MicroLogic 3.2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40
- Depth:
- 86 mm
- Poles Description:
- 3P
- Ambient Air Temperature For Operation:
- -2-70 °C
- Environmental Disclosure:
- ENVPEP2206032EN
- Communication Interface:
- Modbus || Ethernet
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Electrical Connection:
- lugs, line || lugs, load
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Utilisation Category:
- category A
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Suitability For Isolation:
- yes IEC 60947-2
- Continuous Current Rating:
- 0.8
- Circularity Profile:
- ENVEOLI2206032EN
- Line Rated Current:
- 250-250 A
- Mercury Free:
- Yes
- Range:
- PowerPact
- Eu Rohs Directive:
- Compliant with Exemptions
- Device Application:
- distribution
- Mounting Mode:
- unit mount lug)
- Quality Labels:
- CE
- Net Weight:
- 2.4 kg
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Control Type:
- toggle
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity Code:
- D
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View