Schneider Electric JGA36250U31X Molded Case Circuit Breaker 600V 250A
Schneider Electric
$4,226.00
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides Micrologic Standard with a 3.2 trip unit and an LI function with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT J I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Suitability For Isolation:
- yes IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206031EN
- Product Name:
- PowerPact J
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Quality Labels:
- CE
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Height:
- 191 mm
- Mounting Mode:
- I-Line bracket)
- Line Rated Current:
- 250-250 A
- Device Application:
- distribution
- Pollution Degree:
- 3 IEC 60947-1
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Mounting Height:
- 4.5 in
- Sustainable Offer Status:
- Green Premium product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Control Type:
- toggle
- Circularity Profile:
- ENVEOLI2206031EN
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Product Certifications:
- UL || CSA || NOM
- Poles Description:
- 3P
- Rohs Exemption Information:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Pvc Free:
- Yes
- Mounting Support:
- bracket
- Ip Degree Of Protection:
- front cover IP40
- Terminal Identifier:
- AL250JD
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Electrical Connection:
- I-Line connection, line || lugs, load
- Depth:
- 86 mm
- Utilisation Category:
- category A
- Net Weight:
- 2.4 kg
- Warranty:
- 18 months
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Continuous Current Rating:
- 0.8
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Communication Interface:
- Modbus || Ethernet
- Product Or Component Type:
- Motor Circuit Protector
- Trip Unit Name:
- MicroLogic 3.2
- Range:
- PowerPact
- Network Frequency:
- 50/60 Hz
- Wire Stripping Length:
- 25 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Breaking Capacity Code:
- G
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Width:
- 104 mm
- Protection Type:
- overload protection || short-circuit protection
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View