Schneider Electric JGF36225 Molded Case Circuit Breaker 600V 225A
Schneider Electric
$5,668.50
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has a busbar connection. This PowerPacT J, 225A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Width:
- 104 mm
- Product Or Component Type:
- circuit breaker
- Poles Description:
- 3P
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Line Rated Current:
- 225-225 A
- Circuit Breaker Application:
- HACR rated
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Environmental Disclosure:
- ENVPEP2206031EN
- Utilisation Category:
- category A
- Network Frequency:
- 50/60 Hz
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Product Name:
- PowerPact J
- Warranty:
- 18 months
- Suitability For Isolation:
- yes IEC 60947-2
- Continuous Current Rating:
- 0.8
- Ip Degree Of Protection:
- front cover IP40
- Ambient Air Temperature For Operation:
- -2-70 °C
- Sustainable Offer Status:
- Green Premium product
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Range:
- PowerPact
- Depth:
- 86 mm
- Circularity Profile:
- ENVEOLI2206031EN
- Communication Interface:
- Modbus || Ethernet
- Breaking Capacity Code:
- G
- Rohs Exemption Information:
- Yes
- Magnetic Tripping Current:
- 2250-2250 A
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Mercury Free:
- Yes
- Mounting Support:
- busbar
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Control Type:
- toggle
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Pvc Free:
- Yes
- Trip Unit Technology:
- thermal-magnetic
- Wire Stripping Length:
- 25 mm
- Quality Labels:
- CE
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Net Weight:
- 2.4 kg
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Eu Rohs Directive:
- Compliant with Exemptions
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Terminal Identifier:
- AL250JD
- Product Certifications:
- UL || CSA || NOM
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Storage:
- -50-85 °C
- Height:
- 191 mm
- Protection Type:
- overload protection || short-circuit protection
- Pollution Degree:
- 3 IEC 60947-1
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Mode:
- unit mount busbar)
- Device Application:
- distribution
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Magnetic Hold Current:
- 1125 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View