Schneider Electric JGL36200 Molded Case Circuit Breaker 600V 200A
Schneider Electric
$3,779.00
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 200A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Rohs Exemption Information:
- Yes
- Product Or Component Type:
- circuit breaker
- Product Name:
- PowerPact J
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Electrical Connection:
- lugs, line || lugs, load
- Magnetic Hold Current:
- 1000 A
- Poles Description:
- 3P
- Environmental Disclosure:
- ENVPEP2206031EN
- Mounting Mode:
- unit mount lug)
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Width:
- 104 mm
- Product Certifications:
- UL || CSA || NOM
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Control Type:
- toggle
- Eu Rohs Directive:
- Compliant with Exemptions
- Warranty:
- 18 months
- Continuous Current Rating:
- 0.8
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI2206031EN
- Wire Stripping Length:
- 25 mm
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Mounting Support:
- lug
- Pollution Degree:
- 3 IEC 60947-1
- Phase Connection:
- ABC
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Net Weight:
- 2.4 kg
- Depth:
- 86 mm
- Magnetic Tripping Current:
- 2000-2000 A
- Pvc Free:
- Yes
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Terminal Identifier:
- AL250JD
- Circuit Breaker Application:
- HACR rated
- Device Application:
- distribution
- Protection Type:
- overload protection || short-circuit protection
- Suitability For Isolation:
- yes IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity Code:
- G
- Ip Degree Of Protection:
- front cover IP40
- Mercury Free:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- Sustainable Offer Status:
- Green Premium product
- Network Frequency:
- 50/60 Hz
- Line Rated Current:
- 200-200 A
- Quality Labels:
- CE
- Height:
- 191 mm
- Mounting Height:
- 4.5 in
- Trip Unit Technology:
- thermal-magnetic
- Communication Interface:
- Modbus || Ethernet
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Utilisation Category:
- category A
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Range:
- PowerPact
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View