Schneider Electric JGL36225 Molded Case Circuit Breaker 600V 225A
Schneider Electric
$3,779.00
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 225A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Rohs Exemption Information:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Utilisation Category:
- category A
- Product Name:
- PowerPact J
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Network Frequency:
- 50/60 Hz
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Mercury Free:
- Yes
- Pvc Free:
- Yes
- Magnetic Tripping Current:
- 2250-2250 A
- Sustainable Offer Status:
- Green Premium product
- Depth:
- 86 mm
- Product Or Component Type:
- circuit breaker
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Pollution Degree:
- 3 IEC 60947-1
- Trip Unit Technology:
- thermal-magnetic
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Environmental Disclosure:
- ENVPEP2206031EN
- Protection Type:
- overload protection || short-circuit protection
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Mounting Mode:
- unit mount lug)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Communication Interface:
- Modbus || Ethernet
- Device Application:
- distribution
- Width:
- 104 mm
- Terminal Identifier:
- AL250JD
- Control Type:
- toggle
- Range:
- PowerPact
- Net Weight:
- 2.4 kg
- Product Certifications:
- UL || CSA || NOM
- Poles Description:
- 3P
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Ambient Air Temperature For Operation:
- -2-70 °C
- Warranty:
- 18 months
- Ambient Air Temperature For Storage:
- -50-85 °C
- Magnetic Hold Current:
- 1125 A
- Electrical Connection:
- lugs, line || lugs, load
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ip Degree Of Protection:
- front cover IP40
- Wire Stripping Length:
- 25 mm
- Line Rated Current:
- 225-225 A
- Breaking Capacity Code:
- G
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Mounting Support:
- lug
- Height:
- 191 mm
- Continuous Current Rating:
- 0.8
- Circularity Profile:
- ENVEOLI2206031EN
- Suitability For Isolation:
- yes IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Quality Labels:
- CE
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View