Schneider Electric JJL36250M75LC Motor Circuit Protector 600V 250A

(No reviews yet) Write a Review
SKU:
JJL36250M75LC
UPC:
7.85901E+11
Condition:
New
Line Rated Current:
250-250 A
Product Or Component Type:
Motor Circuit Protector
Breaking Capacity:
100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Pvc Free:
Yes
Wire Stripping Length:
25 mm
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Warranty:
18 months
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Suitability For Isolation:
yes IEC 60947-2
Terminal Identifier:
AL250JD
Local Signalling:
switched off (OFF) 1 trip indicator green)
Height:
191 mm
Pollution Degree:
3
Rohs Exemption Information:
Yes
Network Frequency:
50/60 Hz
Environmental Disclosure:
ENVPEP2206031EN
Width:
104 mm
Mercury Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Sustainable Offer Status:
Green Premium product
Ambient Air Temperature For Operation:
-2-70 °C
Mounting Mode:
unit mount lug)
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Poles Description:
3P
[Ith] Conventional Free Air Thermal Current:
117-217 A
Trip Unit Technology:
thermal-magnetic
Circularity Profile:
ENVEOLI2206031EN
Utilisation Category:
category A
Communication Interface:
Modbus
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Product Certifications:
UL || CSA || NOM
Net Weight:
2.4 kg
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Mounting Support:
lug
Eu Rohs Directive:
Compliant with Exemptions
Protection Type:
overload protection || short-circuit protection
Depth:
86 mm
Magnetic Tripping Current:
2500-2500 A
Ip Degree Of Protection:
front cover IP40
Breaking Capacity Code:
J
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
Control Type:
toggle
Accessory / Separate Part Type:
copper lug
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Ambient Air Temperature For Storage:
-50-85 °C
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Continuous Current Rating:
0.8
Electrical Connection:
lugs, line || lugs, load
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Quality Labels:
CE
Magnetic Hold Current:
1250 A
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
  • Schneider Electric JJL36250M75LC Motor Circuit Protector 600V 250A
  • Schneider Electric JJL36250M75LC Motor Circuit Protector 600V 250A
$2,795.00

Description

PowerPacT J-Frame motor circuit protectors (MCP) are instantaneous-trip circuit breakers designed to offer short circuit protection for motors. The unique design of the PowerPacT MCPs accommodates transient motor inrush current without nuisance tripping. These motor protectors accept the same accessories and terminals as the PowerPacT J circuit breakers. This unit has copper lugs on both the line and load side. This PowerPacT J, 250A, 3 pole, motor protector has a breaking capacity of 25kA at 600VAC. The breaker has a continuous current rating of 80%. PowerPacT J motor circuit protectors comply to UL, CSA, and IEC standards and are CE marked.
View AllClose