Schneider Electric JLA262004 Molded Case Circuit Breaker 600V 200A

(No reviews yet) Write a Review
SKU:
JLA262004
UPC:
7.85902E+11
Condition:
New
Breaking Capacity:
125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
Pvc Free:
Yes
Rohs Exemption Information:
Yes
Magnetic Hold Current:
1000 A
Ambient Air Temperature For Operation:
-2-70 °C
Trip Unit Technology:
thermal-magnetic
Suitability For Isolation:
yes IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Phase Connection:
BC
Circuit Breaker Application:
HACR rated
Wire Stripping Length:
25 mm
Mounting Support:
bracket
Communication Interface:
Modbus
Mounting Mode:
I-Line bracket)
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Sustainable Offer Status:
Green Premium product
Quality Labels:
CE
[Ics] Rated Service Breaking Capacity:
125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Height:
191 mm
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Breaking Capacity Code:
L
Mounting Height:
4.5 in
Magnetic Tripping Current:
2000-2000 A
Pollution Degree:
3
Product Certifications:
UL || CSA || NOM
Width:
104 mm
Electrical Connection:
I-Line connection, line || lugs, load
Environmental Disclosure:
ENVPEP2206031EN
Product Or Component Type:
circuit breaker
Continuous Current Rating:
0.8
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Line Rated Current:
200-200 A
Net Weight:
2.4 kg
Local Signalling:
switched off (OFF) 1 trip indicator green)
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Poles Description:
2P
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Protection Type:
overload protection || short-circuit protection
Depth:
86 mm
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Utilisation Category:
category A
Ambient Air Temperature For Storage:
-50-85 °C
Mercury Free:
Yes
Warranty:
18 months
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Terminal Identifier:
AL250JD
Control Type:
toggle
Ip Degree Of Protection:
front cover IP40
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Network Frequency:
50/60 Hz
Circularity Profile:
ENVEOLI2206031EN
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
  • Schneider Electric JLA262004 Molded Case Circuit Breaker 600V 200A
  • Schneider Electric JLA262004 Molded Case Circuit Breaker 600V 200A
$5,985.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 50kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT J I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT J, 200A, 2 pole, circuit breaker has a breaking capacity of 50kA at 600VAC. This circuit breaker has a continuous current rating of 80% with a BC phase connection. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose