- Communication Interface:
- Modbus || Ethernet
- Rohs Exemption Information:
- Yes
- Device Short Name:
- L-Frame
- Mounting Support:
- bracket
- Mounting Mode:
- I-Line bracket)
- Color:
- Black
- Product Name:
- PowerPact L
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Pollution Degree:
- 3 IEC 60947-1
- Circularity Profile:
- ENVEOLI2206029EN
- Device Application:
- distribution
- Width:
- 140 mm
- Sustainable Offer Status:
- Green Premium product
- Eu Rohs Directive:
- Compliant with Exemptions
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Trip Unit Name:
- MicroLogic 3.3
- Warranty:
- 18 months
- Breaking Capacity Code:
- D
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Phase Connection:
- ABC
- Depth:
- 110 mm
- Ip Degree Of Protection:
- front cover IP40
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Mercury Free:
- Yes
- Range:
- PowerPact
- Net Weight:
- 6.2 kg
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Mounting Height:
- 6 in
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Height:
- 340 mm
- Electrical Connection:
- I-Line connection, line || lugs, load
- Ambient Air Temperature For Operation:
- -2-70 °C
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Utilisation Category:
- category A
- Wire Stripping Length:
- 31 mm || 61 mm
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Line Rated Current:
- 400-400 A
- Pvc Free:
- Yes
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Suitability For Isolation:
- yes IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Product Or Component Type:
- circuit breaker
- Network Frequency:
- 50/60 Hz
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Terminal Identifier:
- AL600LS52K3
- Control Type:
- toggle
- Environmental Disclosure:
- ENVPEP2206029EN
- Ambient Air Temperature For Storage:
- -50-85 °C
- Protection Technology:
- current limiter
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Poles Description:
- 3P
- Continuous Current Rating:
- 1