- Ip Degree Of Protection:
- front cover IP40
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Network Frequency:
- 50/60 Hz
- Ambient Air Temperature For Storage:
- -50-85 °C
- Electrical Connection:
- I-Line connection, line || lugs, load
- Device Application:
- distribution
- Device Short Name:
- L-Frame
- Range:
- PowerPact
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Circularity Profile:
- ENVEOLI2206029EN
- Pollution Degree:
- 3 IEC 60947-1
- Utilisation Category:
- category A
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Width:
- 140 mm
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Mounting Mode:
- I-Line bracket)
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Continuous Current Rating:
- 1
- Circuit Breaker Application:
- HACR rated
- Eu Rohs Directive:
- Compliant with Exemptions
- Communication Interface:
- Modbus || Ethernet
- Breaking Capacity Code:
- G
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Trip Unit Name:
- MicroLogic 3.3
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Color:
- Black
- Warranty:
- 18 months
- Mounting Support:
- bracket
- Net Weight:
- 6.2 kg
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Terminal Identifier:
- AL600LS52K3
- [Ue] Rated Operational Voltage:
- 480/277 V AC 50/60 Hz IEC 60947-3
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Line Rated Current:
- 400-400 A
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Product Or Component Type:
- circuit breaker
- Environmental Disclosure:
- ENVPEP2206029EN
- Phase Connection:
- ABC
- Poles Description:
- 3P
- Pvc Free:
- Yes
- Depth:
- 110 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Rohs Exemption Information:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Product Name:
- PowerPact L
- Product Certifications:
- UL || CSA || NOM
- Mounting Height:
- 6 in
- Wire Stripping Length:
- 31 mm || 61 mm
- Control Type:
- toggle
- Height:
- 340 mm
- Sustainable Offer Status:
- Green Premium product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mercury Free:
- Yes
- QN-QUOTE-REQUEST:
- true