[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Warranty:
18 months
Rohs Exemption Information:
Yes
Ambient Air Temperature For Storage:
-50-85 °C
Depth:
110 mm
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Mounting Support:
bracket
Range:
PowerPact
Mounting Mode:
I-Line bracket)
Continuous Current Rating:
0.8
Product Certifications:
UL || CSA || NOM
Breaking Capacity Code:
G
Local Signalling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Ambient Air Temperature For Operation:
-2-70 °C
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Tightening Torque:
50-50 N.m 95-240 mm² (AWG 3/0...500 kcmil)
Poles Description:
3P
Terminal Identifier:
AL600LF52K3
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Height:
340 mm
Ip Degree Of Protection:
front cover IP40
Accessory / Separate Part Type:
padlocking handle ON and OFF end
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Sustainable Offer Status:
Green Premium product
Circularity Profile:
ENVEOLI2206029EN
Pollution Degree:
3 IEC 60947-1
Trip Unit Technology:
electronic, standard, MicroLogic 3.3, LI
Line Rated Current:
400-400 A
Protection Technology:
current limiter
Mounting Height:
6 in
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Mercury Free:
Yes
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Color:
Black
Control Type:
toggle
Width:
140 mm
Awg Gauge:
AWG 3/0...500 kcmil aluminium/copper
Wire Stripping Length:
31 mm
Trip Unit Name:
MicroLogic 3.3
Utilisation Category:
category A
Electrical Connection:
I-Line connection, line || lugs, load
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Communication Interface:
Modbus || Ethernet
Suitability For Isolation:
yes IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Network Frequency:
50/60 Hz
Product Name:
PowerPact L
Circuit Breaker Application:
HACR rated
Device Application:
distribution
Net Weight:
6.2 kg
Phase Connection:
ABC
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Or Component Type:
circuit breaker
Environmental Disclosure:
ENVPEP2206029EN
Device Short Name:
L-Frame
  • Schneider Electric LGA36400U31XYP Molded Case Circuit Breaker 600V 400A
  • Schneider Electric LGA36400U31XYP Molded Case Circuit Breaker 600V 400A
$5,498.00

Description

PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3 trip unit and an LI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. This unit includes a factory installed padlock handle.