Schneider Electric LGL36600U33X Molded Case Circuit Breaker 600V 600A

(No reviews yet) Write a Review
SKU:
LGL36600U33X
UPC:
785901638674
Condition:
New
Network Frequency:
50/60 Hz
Trip Unit Technology:
electronic, standard, MicroLogic 3.3 S, LSI
Product Or Component Type:
circuit breaker
Mounting Support:
lug
Local Signalling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Communication Interface:
Modbus || Ethernet
Suitability For Isolation:
yes IEC 60947-2
Device Short Name:
L-Frame
Rohs Exemption Information:
Yes
Poles Description:
3P
Range:
PowerPact
Sustainable Offer Status:
Green Premium product
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Circuit Breaker Application:
HACR rated
Trip Unit Name:
MicroLogic 3.3 S
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Mounting Mode:
unit mount lug)
Depth:
110 mm
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Utilisation Category:
category A
Tightening Torque:
50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
Product Certifications:
UL || CSA || NOM
Ip Degree Of Protection:
front cover IP40
Breaking Capacity Code:
G
Line Rated Current:
600-600 A
Control Type:
toggle
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Continuous Current Rating:
0.8
Product Name:
PowerPact L
Circularity Profile:
ENVEOLI2206029EN
Protection Technology:
current limiter
Width:
140 mm
Color:
Black
Net Weight:
6.2 kg
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Pollution Degree:
3 IEC 60947-1
Height:
340 mm
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Awg Gauge:
2 x AWG 2/0...500 kcmil aluminium/copper
Eu Rohs Directive:
Compliant with Exemptions
Pvc Free:
Yes
Terminal Identifier:
AL600LS52K3
Device Application:
distribution
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Wire Stripping Length:
31 mm || 61 mm
Mercury Free:
Yes
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Ambient Air Temperature For Operation:
-2-70 °C
Warranty:
18 months
Electrical Connection:
lugs, line || lugs, load
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Environmental Disclosure:
ENVPEP2206029EN
Ambient Air Temperature For Storage:
-50-85 °C
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
  • Schneider Electric LGL36600U33X Molded Case Circuit Breaker 600V 600A
  • Schneider Electric LGL36600U33X Molded Case Circuit Breaker 600V 600A
  • Schneider Electric LGL36600U33X Molded Case Circuit Breaker 600V 600A
$8,077.00

Description

PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 600A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose