Schneider Electric LJM36400U31X Molded Case Circuit Breaker 600V 400A
Schneider Electric
$8,478.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3 trip unit and an LI function. This unit has lugs on the line side and terminal nuts on the load side. This circuit breaker has a continuous current rating of 80%. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Control Type:
- toggle
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Communication Interface:
- Modbus || Ethernet
- Ip Degree Of Protection:
- front cover IP40
- Pollution Degree:
- 3 IEC 60947-1
- Electrical Connection:
- lugs, line || terminal nut, load
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Color:
- Black
- Range:
- PowerPact
- Product Name:
- PowerPact L
- Trip Unit Name:
- MicroLogic 3.3
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Circuit Breaker Application:
- HACR rated
- Net Weight:
- 6.2 kg
- Device Short Name:
- L-Frame
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Warranty:
- 18 months
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Circularity Profile:
- ENVEOLI2206029EN
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity Code:
- J
- Continuous Current Rating:
- 0.8
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Height:
- 340 mm
- Pvc Free:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Width:
- 140 mm
- Rohs Exemption Information:
- Yes
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Terminal Identifier:
- AL600LS52K3
- Ambient Air Temperature For Operation:
- -2-70 °C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mounting Support:
- lug
- Sustainable Offer Status:
- Green Premium product
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Environmental Disclosure:
- ENVPEP2206029EN
- Line Rated Current:
- 400-400 A
- Utilisation Category:
- category A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Depth:
- 110 mm
- Network Frequency:
- 50/60 Hz
- Protection Technology:
- current limiter
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Or Component Type:
- circuit breaker
- Suitability For Isolation:
- yes IEC 60947-2
- Poles Description:
- 3P
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Mounting Mode:
- unit mount lug)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Mercury Free:
- Yes
- Product Certifications:
- UL || CSA || NOM
- Wire Stripping Length:
- 31 mm || 61 mm
- Device Application:
- distribution
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View