Schneider Electric LLA36400U33X Molded Case Circuit Breaker 600V 400A
Schneider Electric
$10,806.00
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 50kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Wire Stripping Length:
- 31 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Device Application:
- distribution
- Mounting Support:
- bracket
- Tightening Torque:
- 50-50 N.m 95-240 mm² (AWG 3/0...500 kcmil)
- Warranty:
- 18 months
- Phase Connection:
- ABC
- Poles Description:
- 3P
- Product Name:
- PowerPact L
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Circularity Profile:
- ENVEOLI2206029EN
- Net Weight:
- 6.2 kg
- Terminal Identifier:
- AL600LF52K3
- Pollution Degree:
- 3 IEC 60947-1
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3 S, LSI
- Height:
- 340 mm
- Mercury Free:
- Yes
- Depth:
- 110 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Mounting Mode:
- I-Line bracket)
- Breaking Capacity Code:
- L
- Control Type:
- toggle
- Awg Gauge:
- AWG 3/0...500 kcmil aluminium/copper
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Rohs Exemption Information:
- Yes
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Ambient Air Temperature For Operation:
- -2-70 °C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Network Frequency:
- 50/60 Hz
- Ip Degree Of Protection:
- front cover IP40
- Utilisation Category:
- category A
- Color:
- Black
- Range:
- PowerPact
- Suitability For Isolation:
- yes IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Width:
- 140 mm
- Mounting Height:
- 6 in
- Environmental Disclosure:
- ENVPEP2206029EN
- Electrical Connection:
- I-Line connection, line || lugs, load
- Device Short Name:
- L-Frame
- Continuous Current Rating:
- 0.8
- Communication Interface:
- Modbus || Ethernet
- Circuit Breaker Application:
- HACR rated
- Sustainable Offer Status:
- Green Premium product
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Line Rated Current:
- 400-400 A
- Trip Unit Name:
- MicroLogic 3.3 S
- Pvc Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View