TeSys U reversing module for side mounting, for the constitution of TeSys U reversing starter controllers. It provides reverse power contacts, coil control with interlocking capabilities to be supplied with 110-240V AC / 110-220V DC. To be used with an advanced power base LUB120, LUB320, or LUB380 equipped with a Control Unit LUC*FU type. To be associated with an assembling connector LU9MR1 and a control terminal block LU9M1 to complete the side mounting. Green Premium compliant (RoHS/REACh).
Ambient Air Temperature For Operation:
-25-60 °C with LUCM || -25-70 °C with LUCA, LUCB, LUCC, LUCD
Network Frequency:
40...60 Hz
Compatibility Code:
LU6MB
[Uc] Control Circuit Voltage:
110...240 V AC 50/60 Hz || 110...220 V DC
Rohs Exemption Information:
Yes
Product Or Component Type:
reverser block
[Ie] Rated Operational Current:
38 A
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Tightening Torque:
control circuit 0.8-1.2 N.m flat 5 mm || control circuit 0.8-1.2 N.m Philips No 2 5 mm || power circuit 1.9-2.5 N.m flat 6 mm || power circuit 1.9-2.5 N.m Philips No 2 6 mm || power circuit 1.9-2.5 N.m pozidriv No 2 6 mm
[Uimp] Rated Impulse Withstand Voltage:
6 kVIEC 60947-6-2
Vibration Resistance:
2 gn 5-300 Hz) power poles open IEC 60068-2-27 || 4 gn 5-300 Hz) power poles closed IEC 60068-2-27
Device Application:
motor control
Current Consumption:
1000 mA 110...220 V DC I maximum while closing || 1000 mA 110...240 V AC I maximum while closing
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mercury Free:
Yes
Warranty:
18 months
Protective Treatment:
TH IEC 60068
Resistance To Fast Transients:
2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4
Non-Dissipating Shock Wave:
1 kV serial mode IEC 60947-6-2 || 2 kV common mode IEC 60947-6-2
Fixing Mode:
clipped DIN rail) || screw-fixed plate)
Net Weight:
0.425 kg
Device Short Name:
LU6MB
Shock Resistance:
10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
Fire Resistance:
960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12
Ip Degree Of Protection:
IP20 IEC 60947-1 front panel and wired terminals) || IP20 IEC 60947-1 other faces) || IP40 IEC 60947-1 front panel outside connection zone)
Inrush Restraint Duration:
25 ms AC || 15 ms DC
Depth:
113 mm
Resistance To Radiated Fields:
10 V/m level 3 IEC 61000-4-3
Ambient Air Temperature For Storage:
-40-85 °C
[Ui] Rated Insulation Voltage:
690 V IEC 60947-6-2 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Device Mounting:
separate mounting
[Ue] Rated Operational Voltage:
690 V AC power circuit
Range:
TeSys
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Operating Time:
150 ms with change of direction || 75 ms without change of direction
Resistance To Electrostatic Discharge:
8 kV level 3, in open air IEC 61000-4-2 || 8 kV level 4, on contact IEC 61000-4-2
Connections - Terminals:
control circuit screw clamp terminals 1 0.34-1.5 mm² 3 mm) flexible with cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² 3 mm) flexible without cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² 3 mm) rigid || cont
Height:
115 mm
Operating Altitude:
6561.68 ft (2000 m)
Eu Rohs Directive:
Compliant with Exemptions
Width:
45 mm
California Proposition 65:
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Product Certifications:
CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
Standards:
EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
Immunity To Radioelectric Fields:
10 V IEC 61000-4-6
Datasheet:
View