Schneider Electric M9F12204 Multi9 C60N 2P D 4A 10Ka 415V Mcb
Schneider Electric
$207.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 4A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
- Heat Dissipation:
- 4.8-4.8 W 415 V - 4 A
- Mounting Support:
- DIN rail
- Utilisation Category:
- category A EN/IEC 60947-2
- Width:
- 36 mm
- Electrical Durability:
- 10000 cycles
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Tightening Torque:
- 2-2 N.m top or bottom
- Pollution Degree:
- 3 EN/IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Ambient Air Temperature For Storage:
- -40-80 °C
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
- Breaking Capacity:
- 20 kA Icu <= 125 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Mechanical Durability:
- 20000 cycles
- Tropicalisation:
- 2 IEC 60068-1
- Range:
- Multi9
- Net Weight:
- 0.24 kg
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Sustainable Offer Status:
- Green Premium product
- Provision For Padlocking:
- padlockable
- Magnetic Tripping Limit:
- 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Network Frequency:
- 50/60 Hz
- Halogen Content Performance:
- Halogen free product
- Earth-Leakage Protection:
- separate block
- Standards:
- EN/IEC 60947-2
- Limitation Class:
- 3
- Local Signalling:
- ON/OFF indication
- Contact Position Indicator:
- yes
- Product Or Component Type:
- miniature circuit-breaker
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Circularity Profile:
- N/A
- Network Type:
- AC || DC
- [Ics] Rated Service Breaking Capacity:
- 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 20 kA 100 % EN/IEC 60947-2 - <= 125 V DC
- Environmental Disclosure:
- ENVPEP1304004EN
- Trip Unit Technology:
- thermal-magnetic
- Line Rated Current:
- 4 A 50 °C EN/IEC 60947-2
- Device Short Name:
- C60N
- Mounting Mode:
- clip-on
- Product Certifications:
- EAC || KC || CCC
- Overvoltage Category:
- IV
- Wire Stripping Length:
- 14 mm for top or bottom connection
- Eu Rohs Directive:
- Compliant with Exemptions
- Relative Humidity:
- 95-95 % 55-55 °C
- Number Of Protected Poles:
- 2
- Color:
- Gray
- Connections - Terminals:
- tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
- Rohs Exemption Information:
- Yes
- Product Name:
- Multi9 C60
- Poles Description:
- 2P
- Curve Code:
- D
- [Ui] Rated Insulation Voltage:
- 500 V AC 50/60 Hz EN/IEC 60947-2
- Control Type:
- toggle
- Mercury Free:
- Yes
- Height:
- 81 mm
- Depth:
- 72 mm
- Device Application:
- distribution
- 9 Mm Pitches:
- 4
- Ambient Air Temperature For Operation:
- -30-70 °C
- Brochure:
- View
- Datasheet:
- View