Standards:
EN/IEC 60947-2 || GB 14048.2 || UL 489 || CSA C22.2 No 5
Provision For Padlocking:
padlockable
Local Signalling:
ON/OFF indication
Number Of Protected Poles:
1
Depth:
72 mm
Ip Degree Of Protection:
IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
Environmental Disclosure:
ENVPEP1304004EN
Mounting Support:
DIN rail
Ambient Air Temperature For Operation:
-30-70 °C
[Ui] Rated Insulation Voltage:
500 V AC EN/IEC 60947-2
Product Or Component Type:
miniature circuit-breaker
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Trip Unit Technology:
thermal-magnetic
Magnetic Tripping Limit:
3 x In +/- 20 % AC || 4.2 x In +/- 20 % DC
Mechanical Durability:
20000 cycles
Suitability For Isolation:
yes EN/IEC 60947-2
[Ue] Rated Operational Voltage:
240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 60 V DC
Operating Altitude:
0...6561.68 ft (0...2000 m)
Control Type:
toggle
Color:
Gray
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mercury Free:
Yes
Wire Stripping Length:
14 mm for top or bottom connection
Height:
103 mm
Tropicalisation:
2 IEC 60068-1
[Uimp] Rated Impulse Withstand Voltage:
6 kVEN/IEC 60947-2
Product Certifications:
IEC || CCC || CSA || UL
Width:
18 mm
Electrical Durability:
10000 cycles
Product Name:
Multi9 C60
Rohs Exemption Information:
Yes
Ambient Air Temperature For Storage:
-40-80 °C
Earth-Leakage Protection:
without
Device Application:
distribution
Network Type:
DC || AC
Tightening Torque:
3.5-3.5 N.m top or bottom
Eu Rohs Directive:
Compliant with Exemptions
Relative Humidity:
95-95 % 55-55 °C
[Ics] Rated Service Breaking Capacity:
2.25 kA 75 % EN/IEC 60947-2 - 415 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 240 V AC || 2.25 kA 75 % GB 14048.2 - 415 V AC || 7.5 kA 75 % GB 14048.2 - 240 V AC || 15 kA 75 % GB 14048.2 - 60 V DC || 15 kA 75 % EN/IEC 60947-2 - 60 V DC
Curve Code:
Z
Mounting Mode:
clip-on
9 Mm Pitches:
2
Halogen Content Performance:
Halogen free product
Connections - Terminals:
tunnel type terminal top or bottom) 1-35 mm² AWG 18...AWG 2) - rigid || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 3) - flexible with ferrule || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 3) - flexible
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Device Short Name:
C60BP
Contact Position Indicator:
yes
Poles Description:
1P
Pollution Degree:
3 EN/IEC 60947-2
Breaking Capacity:
3 kA Icu 415 V AC EN/IEC 60947-2 || 10 kA Icu 240 V AC EN/IEC 60947-2 || 20 kA Icu 60 V DC EN/IEC 60947-2 || 3 kA Icu 415 V AC GB 14048.2 || 10 kA Icu 240 V AC GB 14048.2 || 20 kA Icu 60 V DC GB 14048.2 || 10 kA AIR 60 V DC UL 489 || 10 kA AIR 240 V
Circularity Profile:
N/A
Sustainable Offer Status:
Green Premium product
Range:
Multi9
Line Rated Current:
63 A 25 °C EN/IEC 60947-2
Brochure:
View
Datasheet:
View
$180.00

Description

This Multi9 C60BP is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 63A rated current and Z tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 standard and 3kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 103mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.