Schneider Electric M9U21270 Multi9 C60H-Dc 2P 0,5A C 10Ka 500Vdc Mcb
Schneider Electric
$588.00
This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 2P circuit breaker with 2 protected poles, 0.5A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 20kA at 220VDC conforming to EN/IEC 60947-2 standard and 20kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.
- Mercury Free:
- Yes
- Relative Humidity:
- 95-95 % 55-55 °C
- Tropicalisation:
- 2 IEC 60068-2 || 2 GB 14048.2
- Device Application:
- distribution
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Toxic Heavy Metal Free:
- Yes
- Provision For Padlocking:
- padlockable
- Reach Free Of Svhc:
- Yes
- Color:
- Gray
- Net Weight:
- 0.128 kg
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Height:
- 81 mm
- Contact Position Indicator:
- yes
- Environmental Disclosure:
- ENVPEP120608EN_V0
- Control Type:
- toggle
- Ambient Air Temperature For Storage:
- -40-85 °C
- Ambient Air Temperature For Operation:
- -25-70 °C
- [Ui] Rated Insulation Voltage:
- 500 V DC EN/IEC 60947-2
- Poles Description:
- 2P
- Local Signalling:
- ON/OFF indication
- Circularity Profile:
- N/A
- Curve Code:
- C
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Mechanical Durability:
- 20000 cycles
- Line Rated Current:
- 0.5 A 25 °C EN/IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Mounting Mode:
- clip-on
- Wire Stripping Length:
- 14 mm for top or bottom connection
- Earth-Leakage Protection:
- without
- Electrical Durability:
- 3000 cycles 250 V DC L/R = 2 ms || 6000 cycles 250 V DC
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Utilisation Category:
- category A EN/IEC 60947-2
- Mounting Support:
- DIN rail
- [Ics] Rated Service Breaking Capacity:
- 7.5 kA 75 % EN/IEC 60947-2 - 440 V DC || 4.5 kA 75 % EN/IEC 60947-2 - 500 V DC || 15 kA 75 % EN/IEC 60947-2 - 220 V DC || 7.5 kA 75 % GB 14048.2 - 440 V DC || 4.5 kA 75 % GB 14048.2 - 500 V DC || 15 kA 75 % GB 14048.2 - 220 V DC
- Product Certifications:
- IEC || CCC || UR
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Depth:
- 73 mm
- Sustainable Offer Status:
- Green Premium product
- Rohs Exemption Information:
- Yes
- Product Name:
- Multi9 C60H-DC
- Number Of Protected Poles:
- 2
- [Ue] Rated Operational Voltage:
- 220 V DC || 440 V DC || 500 V DC
- Width:
- 36 mm
- Connections - Terminals:
- tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - rigid stranded || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 6) - flexible || tunnel type terminal top or bottom) 1-16 mm² AWG 18...AWG 6) - flexible with ferrule || tun
- Tightening Torque:
- 2.5-2.5 N.m top or bottom
- Range:
- Multi9
- Heat Dissipation:
- 4.4-4.4 W 440 V - 0.5 A
- Pollution Degree:
- 3 EN/IEC 60947-2
- Eu Rohs Directive:
- Compliant
- Product Or Component Type:
- miniature circuit-breaker
- Magnetic Tripping Limit:
- 7...10 x In DC
- 9 Mm Pitches:
- 4
- Breaking Capacity:
- 20 kA Icu 220 V DC EN/IEC 60947-2 || 10 kA Icu 440 V DC EN/IEC 60947-2 || 6 kA Icu 500 V DC EN/IEC 60947-2 || 5 kA AIR 12...500 V DC UL 1077 || 20 kA Icu 220 V DC GB 14048.2 || 10 kA Icu 440 V DC GB 14048.2 || 6 kA Icu 500 V DC GB 14048.2
- Standards:
- EN/IEC 60947-2 || GB 14048.2 || UL 1077
- Network Type:
- DC
- Device Short Name:
- C60H-DC
- Brochure:
- View
- Datasheet:
- View