- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Mounting Support:
- bracket
- Ambient Air Temperature For Storage:
- -50-85 °C
- Warranty:
- 18 months
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Breaking Capacity Code:
- G
- Poles Description:
- 3P
- Terminal Identifier:
- AL800M23K
- Mercury Free:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Circuit Breaker Application:
- HACR rated
- Line Rated Current:
- 800-800 A
- Pvc Free:
- Yes
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Sustainable Offer Status:
- Green Premium product
- Range:
- PowerPact
- Device Application:
- distribution
- Magnetic Tripping Current:
- 1600-8000 A
- Quality Labels:
- CE
- Local Signalling:
- 1 trip indicator green)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Environmental Disclosure:
- ENVPEP2206030EN
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Network Frequency:
- 50/60 Hz
- Utilisation Category:
- category A
- Circularity Profile:
- ENVEOLI2206030EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Wire Stripping Length:
- 25 mm
- Depth:
- 8.05 in
- Product Name:
- PowerPact M
- Quantity Per Set:
- 1
- Control Type:
- operating handle
- Electrical Connection:
- I-Line connection, line || lugs, load
- Trip Unit Name:
- ET 1.0
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Ip Degree Of Protection:
- IP40
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Height:
- 9 in
- Mounting Mode:
- I-Line bracket)
- Height:
- 12.86 in
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Width:
- 8.27 in
- Color:
- Black
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Operation:
- -25-70 °C
- Rohs Exemption Information:
- Yes
- Continuous Current Rating:
- 0.8
- Net Weight:
- 29 lb(US)