Schneider Electric

Schneider Electric MGF36800E10 Molded Case Circuit Breaker 600V 800A

(No reviews yet) Write a Review
SKU:
MGF36800E10
UPC:
3606486284872
Condition:
New
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Rohs Exemption Information:
Yes
Trip Unit Technology:
electronic, basic, ET 1.0,
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Magnetic Tripping Current:
1600-8000 A
Utilisation Category:
category A
Circularity Profile:
ENVEOLI2206030EN
Trip Unit Name:
ET 1.0
Width:
8.27 in
Electrical Connection:
busbar connection, line || busbar connection, load
Product Certifications:
UL || CSA || NOM
Height:
12.86 in
Range:
PowerPact
Mounting Support:
busbar
Color:
Black
Terminal Identifier:
AL800M23K
Ambient Air Temperature For Operation:
-25-70 °C
Suitability For Isolation:
yes IEC 60947-2
Ip Degree Of Protection:
IP40
Mounting Mode:
unit mount busbar)
Communication Interface:
Modbus
Net Weight:
29 lb(US)
Breaking Capacity Code:
G
Mercury Free:
Yes
Ambient Air Temperature For Storage:
-50-85 °C
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Depth:
8.05 in
Pollution Degree:
3 IEC 60947-1
Poles Description:
3P
Local Signalling:
1 trip indicator green)
Pvc Free:
Yes
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
Wire Stripping Length:
25 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Line Rated Current:
300-800 A
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
Product Name:
PowerPact M
Device Application:
distribution
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
Environmental Disclosure:
ENVPEP2206030EN
Quality Labels:
CE
Network Frequency:
50/60 Hz
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Awg Gauge:
3 x AWG 3/0...3 x 500 kcmil aluminium/copper
Accessory / Separate Part Type:
communication module
Product Or Component Type:
circuit breaker
Long Time Pick-Up Adjustment Range:
300...800 A
Continuous Current Rating:
0.8
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
Sustainable Offer Status:
Green Premium product
Quantity Per Set:
1
Control Type:
operating handle
Eu Rohs Directive:
Compliant with Exemptions
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Circuit Breaker Application:
HACR rated
Catalog:
View
Datasheet:
View
$7,719.00

Description

PowerPacT M-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT M-Frame circuit breakers have either a fixed long time electronic trip unit or an adjustable amperage version. This circuit breaker has the adjustable amperage option, allowing trip setting changes between 300A to 800A using a selector switch. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT M circuit breakers are available in 2 and 3-pole unit mount or I-Line construction. This unit has a busbar connection. This PowerPacT M, 300A to 800A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT M circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose