- Continuous Current Rating:
- 0.8
- Control Type:
- operating handle
- Utilisation Category:
- category A
- Height:
- 12.86 in
- Mounting Mode:
- unit mount lug)
- Net Weight:
- 29 lb(US)
- Circuit Breaker Application:
- HACR rated
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Depth:
- 8.05 in
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Certifications:
- UL || CSA || NOM
- Wire Stripping Length:
- 25 mm
- Pvc Free:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Quality Labels:
- CE
- Product Name:
- PowerPact M
- Line Rated Current:
- 700-700 A
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Mercury Free:
- Yes
- Network Frequency:
- 50/60 Hz
- Width:
- 8.27 in
- Terminal Identifier:
- AL800M23K
- Circularity Profile:
- ENVEOLI2206030EN
- Pollution Degree:
- 3 IEC 60947-1
- Quantity Per Set:
- 1
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Poles Description:
- 3P
- Warranty:
- 18 months
- Trip Unit Name:
- ET 1.0
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Or Component Type:
- circuit breaker
- Suitability For Isolation:
- yes IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206030EN
- Mounting Support:
- lug
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Ambient Air Temperature For Storage:
- -50-85 °C
- Eu Rohs Directive:
- Compliant with Exemptions
- Ambient Air Temperature For Operation:
- -25-70 °C
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Local Signalling:
- 1 trip indicator green)
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Rohs Exemption Information:
- Yes
- Range:
- PowerPact
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Magnetic Tripping Current:
- 1400-7000 A
- Ip Degree Of Protection:
- IP40
- Device Application:
- distribution
- Electrical Connection:
- lugs, load || lugs, line
- Breaking Capacity Code:
- G
- Color:
- Black
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- QN-QUOTE-REQUEST:
- true