Schneider Electric MGP36800 Molded Case Circuit Breaker 600V 800A
Schneider Electric
$9,927.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT M-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT M-Frame circuit breakers have either a fixed long time electronic trip unit or an adjustable amperage version. This circuit breaker has an electronic trip unit, ET 1.0. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT M circuit breakers are available in 2 and 3-pole unit mount or I-Line construction. This unit has terminal nuts on the line side and lugs on the load side. This PowerPacT M, 800A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT M circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Depth:
- 8.05 in
- Mounting Support:
- lug
- Eu Rohs Directive:
- Compliant with Exemptions
- Environmental Disclosure:
- ENVPEP2206030EN
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Device Application:
- distribution
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Name:
- PowerPact M
- Quality Labels:
- CE
- Sustainable Offer Status:
- Green Premium product
- Product Or Component Type:
- circuit breaker
- Ip Degree Of Protection:
- IP40
- Range:
- PowerPact
- Quantity Per Set:
- 1
- Color:
- Black
- Terminal Identifier:
- AL800M23K
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Breaking Capacity Code:
- G
- Ambient Air Temperature For Storage:
- -50-85 °C
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Rohs Exemption Information:
- Yes
- Mounting Mode:
- unit mount lug)
- Poles Description:
- 3P
- Pvc Free:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Line Rated Current:
- 800-800 A
- Circularity Profile:
- ENVEOLI2206030EN
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Warranty:
- 18 months
- Ambient Air Temperature For Operation:
- -25-70 °C
- Width:
- 8.27 in
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Magnetic Tripping Current:
- 1600-8000 A
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Mercury Free:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Local Signalling:
- 1 trip indicator green)
- Height:
- 12.86 in
- Suitability For Isolation:
- yes IEC 60947-2
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Control Type:
- operating handle
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Electrical Connection:
- terminal nut, line || lugs, load
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Net Weight:
- 29 lb(US)
- Network Frequency:
- 50/60 Hz
- Circuit Breaker Application:
- HACR rated
- Utilisation Category:
- category A
- Continuous Current Rating:
- 0.8
- Product Certifications:
- UL || CSA || NOM
- Wire Stripping Length:
- 25 mm
- Trip Unit Name:
- ET 1.0
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View